VIKING RANGE, LLC

Downdraft Ventilators

1.  The interior  down-

draft blower system is 
designed for use with 
3-1/4" x 10" duct-
work (can be transi-
tioned to 6" round). 
Three different dis-
charge directions are 
available with side-to-
side adjustment for 
accurate alignment of 
ductwork.

2.  For best perfor-

mance: Choose the 
ducting option which 
allows the shortest 
length of ductwork 

RIGHT

DISCHARGE

DOWN DISCHARGE

LEFT

DISCHARGE

PLAN THE DUCTWORK

Interior Blower Installation

Exterior Blower Installation

10" ROUND

DISCHARGE 

PLATE

1.  The exterior downdraft 

blower system is designed 
for use with 10" round 
ductwork.

2.  For best performance: 

Plan ducting which has the 
shortest length of ductwork 
and a minimum number of 
elbows. Check location of 
fl oor joists, wall studs, elec-
trical wiring or plumbing 
for possible interference. 

EQUALS 6 FT. OF 

STRAIGHT DUCT

10" ROUND

ELBOW

EQUALS 6 FT. OF 

STRAIGHT DUCT

6" ROUND 

ELBOW

EQUALS 8 FT. OF

STRAIGHT DUCT

3.  The system will operate most effi ciently when the ductwork 

does not exceed 40 feet of equivalent duct. The chart, above, 
shows equivalent feet of elbows and transitions. The number 
of feet of straight duct plus the equivalent feet of transitions 
and/or elbows to be used should equal 40 feet or less.

NOTE: The equivalent feet of various roof and wall caps has 
been taken into consideration. Do not include them in this 
calculation.

3-1/4" X 10" TO 6" RD. 
TRANSITION

3-1/4" X 10"

90

O

 ELBOW

29   "

5

16

2   "

1
8

VIDV500

INTERNAL

BLOWER

5"

2"

1"

3   "

1

4

3   "

5

8

1
4

7   "

11
16

18"

FROM

COUNTERTOP

TO BOTTOM

OF AIR BOX

"

29   "

5

16

2   "

1
8

2"

1"

3   "

1

4

3   "

5

8

1
4

7   "

11
16

FROM

COUNTERTOP

TO BOTTOM

OF AIR BOX

"

3   "

3

16

1
4

"

13

1
4

"

13

1   "

9

16

10" ROUND

ELBOW

and a minimum number of elbows and transitions. Check 
location of fl oor joists, wall studs, electrical wiring or 
plumbing for possible interference. 

3.  The system will operate most effi ciently when the ductwork 

does not exceed 40 feet of equivalent duct. The illustration, 
above, shows equivalent feet of a 10" round elbow. The 
number of feet of straight duct plus the equivalent feet of 
elbows to be used should equal 40 feet or less.

NOTE: The equivalent feet of various roof and wall caps has 
been taken into consideration. Do not include them in this 
calculation.

Interior Blower Installation

Exterior Blower Installation

TAKE MEASUREMENTS 

(CONTINUED)

EQUALS
2 FT. OF
STRAIGHT DUCT

SIDE VIEW

OF DOWNDRAFT

WITH

VIDV500

INTERIOR

BLOWER

SIDE VIEW

OF DOWNDRAFT

WITH

10" ROUND ELBOW

(for connection 
to VEDV900 or 

VEDV1200 Exterior 

Blower)

VIDV500

INTERIOR

BLOWER

Содержание VIPR102

Страница 1: ...r d Use proper pan size Always use cookware appropriate for the size of the surface element TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE OBSERVE THE FOLLOWINGa 1 SMO...

Страница 2: ...ps It can be mounted in island peninsula or conventional wall locations Thisunitcanbeeasilyinstalled following these basic steps Cut out the countertop opening Mount the unit in the cabinet Install 10...

Страница 3: ...equivalent feet of transitions and or elbows to be used should equal 40 feet or less NOTE The equivalent feet of various roof and wall caps has been taken into consideration Do not include them in thi...

Страница 4: ...P 10 CENTER LINE OF COUNTER CUTOUT CENTER LINE OF DUCT CUTOUT 2 10 10 ROUND DIA CUTOUT TYP 3 6 CENTER LINE OF DUCT CUTOUT can be located within this area CENTER LINE OF COUNTER CUTOUT 19 10 10 ROUND C...

Страница 5: ...LOCATION OF ELECTRICAL OUTLET If Models VIPR102SS or VIPR102RSS are being installed in a 30 wide cabinet or Models VIPR162SS or VIPR162RSS are being installed in a 36 wide cabinet or Models VIPR182SS...

Страница 6: ...r cover 4 Carefully position the10 discharge plate under the bottom flange of the downdraft 5 Connect motor plug 6 Replace the gear motor cover and 2 sheet metal screws 7 Replace the 2 clamp channels...

Страница 7: ...4 30 36 48 B 20 1 4 20 1 4 18 3 4 18 3 4 24 24 24 C 27 33 27 33 27 33 45 D 2 1 4 2 1 4 3 3 2 3 4 2 3 4 2 3 4 E 7 8 7 8 1 1 2 1 1 2 1 1 2 F 7 8 7 8 1 1 16 1 1 4 1 1 2 1 1 2 1 1 2 A C B D F E A C B D F...

Страница 8: ...m secure and air tight 3 Connect ductwork to downdraft If necessary LOOSEN nuts and screws that hold remote blower adapter plate in place and slide outlet assembly left or right to meet ductwork Re ti...

Страница 9: ...the paper from the adhesive back of the control line the control up with the three holes and position the control so it is parallel with the front of the counter top Press down firmly for 60 seconds 4...

Страница 10: ...10 Downdraft Ventilators VIKING RANGE LLC This page has been left blank intentionally BACKSIDE OF REMOTE SWITCH TEMPLATE...

Страница 11: ...und power cable from the remote blower to wiring box on 10 round discharge plate 5 Connectdowndraftwiringtopowercablefromremoteblower Wire black to black white to white and green to green or bare wire...

Страница 12: ...e it first Reverse the steps under MOUNT THE UNIT to remove the downdraft from the cabinet All Units OPERATION All Units UP DOWN Raisesandlowers vent Turns blower ON when vent is UP and OFF when vent...

Страница 13: ...whether arising out of breach of warranty breach of contract or otherwise Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or...

Страница 14: ...ri e Toujours utiliser une batterie de cuisine proportionnelle l l ment de surface AFIN DE DIMINUER LES RISQUES DE BLESSURES POUVANT SURVENIR LORSQU UN FEU SE D CLENCHE SUR LA SURFACE DE CUISSON SUIVE...

Страница 15: ...surface de cuisson COMPTOIR BOUCHE DE CHEMIN E CONDUIT ROND DE 25 4 cm 10 po PLAQUE D VACUATION DE 25 4 cm 10 po SP CIFICATIONS LECTRIQUES 120 VCA 60 Hz 6 0 A max SP CIFICATIONS LECTRIQUES 120 VCA 60...

Страница 16: ...SUITE GALE UN CONDUIT DROIT DE 61 CM 2 PI VUE DE C T DE LA HOTTE AVEC VENTILATEUR INT RIEUR VIDV500 VUE DE C T DE LA HOTTE AVEC COUDE ROND DE 25 4 cm 10 po pour connexion au ventilateur ext rieur VEDV...

Страница 17: ...ancher les montants des murs les c bles lectriques et les tuyaux de nuisent pas Ventilateurs encastr s 61 2 cm 24 1 8 po LIGNE DE CENTRE DU D COUPAGE DU COMPTOIR 14 cm 5 1 2 po LIGNES DE CENTRE DU D C...

Страница 18: ...s mod les VIPR102SS ou VIPR102RSS sont install s dans une armoire de 76 2 cm 30 po de largeur ou les mod les VIPR162SS ou VIPR162RSS sont instal l s dans une armoire de 91 4 cm 36 po de largeur ou les...

Страница 19: ...s la bride inf rieure de la hotte 5 Branchez la prise du moteur 6 Replacez le couvercle du moteur et les 2 vis m tal 7 Replacez les 2 profil s et engagez les 4 crous sans serrer 8 Glissez le ventilate...

Страница 20: ...3 8 cm 33po 114 3 cm 45po D 5 7 cm 2 po 5 7 cm 2 po 7 6 cm 3 po 7 6 cm 3 po 7 cm 2 po 7 cm 2 po 7 cm 2 po E 2 2 cm 7 8 po 2 2 cm 7 8 po 3 8 cm 1 po 3 8 cm 1 po 3 8 cm 1 po F 2 2 cm 7 8 po 2 2 cm 7 8 p...

Страница 21: ...hes 3 Raccordez le conduit la hotte Au besoin DESSERREZ les crous et les vis qui maintiennent la plaque d adaptateur du ventilateur et glissez la gauche ou droite pour l aligner avec le conduit Resser...

Страница 22: ...trique de la plaque d vacuation de 25 4 cm 10 po de diam tre 5 Raccordez les fils de la hotte au c ble d alimentation du ventilateur Raccordez le noir avec le noir le blanc au blanc et le vert au vert...

Страница 23: ...s et vitez les endroits o un chaudron chaud pourrait tre d pos ou des liquides chauds renvers s 4 Sortez les deux crous en nylon du sachet de plastique et installez les sur les goujons de la t l comma...

Страница 24: ...24 Downdraft Ventilators VIKING RANGE LLC Ventilateurs encastr s Cette page a t laiss e en blanc volontairement ARRI RE DU GABARIT DE LA T L COMMANDE...

Страница 25: ...s mod les FONCTIONNEMENT Tous les mod les HAUT BAS Rel ve ou abaisse l e c o n d u i t d a ration Met le ventilateur en MARCHE lorsque le conduit est RELEV et ARR TE le ventilateur lorsque le conduit...

Страница 26: ...inobservation d une garantie de la violation d un contrat ou de toute autre cause Certaines juridictions interdisant l exclusion ou la limitation des dommages indirects ou cons cutifs il se peut que...

Страница 27: ...tama o adecuado Siempre use utensilios de cocina que sean apropiados para el tama o del elemento de la superficie TPARA REDUCIR EL RIESGO DE LESIONES A PERSONAS EN CASO DE UN INCENDIO PRODUCIDO POR G...

Страница 28: ...estos pasos b sicos Monte la unidad en el gabinete Instale la placa de descarga redonda de 10 pulg 25 cm Instale el ventilador exterior modelo VEDV900 o VEDV1200 s lo el modelo de 48 pulg 120 cm Cone...

Страница 29: ...e ha tomado en consideraci n la longitud equivalente en pies de varias tapas de techo y pared No las incluya en este c lculo TRANSICI N REDONDA DE 3 1 4 X 10 pulg 8 2 x 25 cm A 6 pulg 15 2 cm 1 pulg 2...

Страница 30: ...GABINETE L NEA CENTRAL DEL CORTE PARA EL CONDUCTO 2 pulg 7 cm RECORTE REDONDO DE 10 pulg 25 cm T pico 3 pulg 8 9 cm 6 pulg 15 9 cm L NEA CENTRAL DEL CORTE DEL CONDUCTO se puede situar dentro de esta r...

Страница 31: ...SS se van a instalar en un gabinete de 30 pulg 75 cm de ancho o si los modelos VIPR162SS o VIPR162RSS se van a instalar en un gabinete de 36 pulg 90 cm de ancho o si los modelos VIPR182SS o VIPR182RSS...

Страница 32: ...de inferior del tiro descendente 5 Conecte el enchufe del motor 6 Vuelva a colocar la cubierta del motor de engranaje y los 2 tornillos autorroscantes 7 Vuelva a colocar los 2 canales de sujeci n y ap...

Страница 33: ...C 27 pulg 68 6 cm 33 pulg 83 8 cm 27 pulg 68 6 cm 33 pulg 83 8 cm 27 pulg 68 6 cm 33 pulg 83 8 cm 45 pulg 114 3 cm D 2 1 4 pulg 5 7 cm 2 1 4 pulg 5 7 cm 3 pulg 7 6 cm 3 pulg 7 6 cm 2 3 4 pulg 7 cm 2 3...

Страница 34: ...s al tiro descendente Si es necesario AFLOJE las tuercas y los tornillos que fijan la placa adaptadora del ventilador remoto en su lugar y deslice el conjunto de la salida hacia la izquierda o hacia l...

Страница 35: ...orificios y coloque el control de tal manera que quede paralelo con el frente del gabinete Oprima firmemente durante 60 segundos 4 Saque las dos tuercas de mariposa de nailon de la bolsa de pl stico y...

Страница 36: ...36 Ventiladores de tiro descendente VIKING RANGE LLC Esta p gina se ha dejado en blanco intencionalmente PARTE POSTERIOR DE LA PLANTILLA DEL CONMUTADOR REMOTO...

Страница 37: ...de cableado en una placa de descarga de 10 pulg 25 cm 5 Conecte el cableado del tiro descendente al cable el ctrico desde el ventilador remoto Conecte negro con negro blanco con blanco y verde con ve...

Страница 38: ...o descendente del gabinete Todas las unidades FUNCIONAMIENTO Todas las unidades ARRIBA ABAJO Subeybajaelsistema de ventilaci n Enciendeelventilador cuando el sistema est ARRIBA y lo apaga cuando el si...

Страница 39: ...o incidentales que surjan por el incumplimiento de la garant a incumplimiento de contrato o de otra manera Algunas jurisdicciones no permiten la exclusi n o limitaci n de da os incidentales o consecue...

Страница 40: ...Las especificaciones est n sujetas a cambios sin previo aviso Si desea m s informaci n sobre el producto llame al 1 845 4641 o visite el sitio web en http www vikingrange com 99044605C F20073C SP...

Отзывы: