background image

1. PRO DUCT NAME

Vi king Model S-1 Early Sup pres sion
Fast Re sponse Pen dent Sprin klers
(K = 14.0) 

Sprin kler Base P/N 10284 (SIN VK500†)
FM and LPCB Ap proved and UL/C-UL
Listed (With out an ejec tor spring)

Sprin kler Base P/N 11350 (SIN VK500†)
FM and VdS Ap proved (With an ejec -
tor spring)

Avail able since 2000.

†The Sprin kler Iden ti fi ca tion Num ber (SIN) is

stamped on the sprin kler deflector. 

2. MAN U FAC TURER

The Vi king Cor po ra tion
210 N. In dus trial Park Road
Hastings, Mich i gan 49058 USA
Tele phone: 

 (269) 945-9501

 (877) 384-5464

Fax:

 (269) 945-9599

e-mail: [email protected]

3. PRO DUCT DE SCRIP TION

Vi king Early Sup pres sion Fast  Re -
sponse (ESFR) Pendent Sprin kler SIN
VK500 is a fast re sponse fus ible el e -
ment type sprin kler de signed for early
fire sup pres sion.
With a 14.0 nom i nal K-Factor and spe -
cial de flec tor, this sprin kler pro duces
large, high-momentum wa ter drop lets in

a hemi spheric pat tern be low the de flec -
tor. This per mits pen e tra tion of the fire
plume and di rect wet ting of the burn ing
fuel sur face while cool ing the at mo -
sphere early in the de vel op ment of a
high-challenge fire.
Vi king SIN VK500 ESFR Pen dent Sprin -
klers may be used in the pro tec tion of or -
di nary types of stor age. How ever, they
are pri mar ily in tended to pro tect the fol -
low ing types of stor age, which tend to
pro duce se vere-challenge fires:
palletized and solid pile stor age and sin -
gle, dou ble, mul ti ple row, and por ta ble
rack stor age (no open-top con tain ers or
solid shelves).
Vi king ESFR Pen dent SIN VK500 Sprin -
klers pro vide pro tec tion of most com -
mon stor age ma te ri als, in clud ing: 

En cap su lated or unencapsulated
Class I, II, III, and IV com mod i ties*.

Cartoned and uncartoned un ex pand -
ed plas tics*.

Cartoned and uncartoned ex panded
plas tics*.

In ad di tion, some stor age ar range ments 
of rolled pa per, aero sols, and rub ber
tires may be pro tected by Vi king ESFR
Pen dent Sprin kler SIN VK500.

ESFR Pen dent Sprin kler Base Part No.
10284 is FM and LPCB Ap proved and
UL/C-UL Listed, while Part No. 11350 is
FM and VdS Ap proved for:

Pro tecting rack stor age of cer tain
spec i fied ma te ri als up to 35 ft (10,7 m)
high in build ings with 40 ft (12,2 m)
high ceil ings with no in-rack sprin -
klers*.

TECH NI CAL DATA

ESFR PEN DENT SPRIN KLERS

SIN VK500 (K = 14.0)

Sprin kler Temp.

Clas si fi ca tion

Nom i nal Tem per a ture

Rat ing (Fusing Point)

2

Max i mum Am bi ent

Ceil ing Tem per a ture

1

Frame Paint Color

Ordinary

165 °F (74 °C)

100 °F (38 °C)

None

In ter me di ate

10

205 °F (96 °C)

150 °F (65 °C)

White

Ap proval Chart

Vi king ESFR Pen dent Sprin kler SIN VK500

Pen dent De flec tor

NPT Thread

Size

Sprin kler Base

Part Number

3

SIN

Nom i nal

K-Factor

List ings and Approvals

4,5

Fast Re sponse

Fus ible Element

Inch

mm

U.S.

met ric

6

FM

VdS

cULus

7

NYC

8

LPCB

3/4

20

10284

VK500

14.0

A1, B1

A1, B1

A1

A1

11350

VK500

20,2

A1

A1

A1

Ap proved Tem per a ture Rat ings

A - 165 °F (74 °C)             B - 205 °F (96 °C)

9

Ap proved Fin ish

1 - Brass

Foot notes

Based on NFPA-13. Other lim its may ap ply, de pend ing on fire load ing, sprin kler lo ca tion, and other re quire ments of the Au thor ity Hav ing
Ju ris dic tion. Re fer to spe cific in stal la tion stan dards.

The tem per a ture rat ing is stamped on the de flec tor.

3

 Base part num ber shown. For com plete part num ber, re fer to Vi king’s cur rent price sched ule.

This chart shows listings and ap provals avail able at the time of print ing.

5

 Re fer to the latest standards of NFPA 13, appli ca ble FM Global Loss Pre ven tion Data Sheets, LPCB Loss Prevention Standards, and the latest

standards of Verband der Sachversicherer.

6

  Met ric K-Factor shown is for use w hen pres sure is mea sured in kPa. When pres sure is measured in BAR, mul ti ply the met ric K-Factor shown by 10.0.

7

 Listed by Un der writers Lab o ra tories Inc. for use in the U.S. and Can ada. 

8

 Ac cepted for use, City of New York De part ment of Build ings, MEA 89-92-E, Vol. XVIII.

9

 The intermediate temperature rating is available for Sprinkler Base Part Number 10284 only.

                         

 Tem per a ture              

KEY

                  Fin ish

 

 A1X

 

      Es cutch eon (if ap pli ca ble)

Sprin kler Base Part No. 10284

(Shown with or di nary tem per a ture

rated el e ment.) Sprin kler Base Part

No. 11350 is sim i lar, how ever,

it has an ejector spring. 

De cem ber 10, 2004

Sprin kler 120 a

Note: Units of mea sure in pa ren the ses may be ap prox i ma tions.

Form No. F_060198

Re places sprin kler page 120 a-d, dated Feb ru ary 20, 2004
(referenced NFPA 13 ex cep tions to ESFR sprin kler spac ing rules).

Содержание SIN VK500

Страница 1: ... specified materials up to 35 ft 10 7 m high in buildings with 40 ft 12 2 m high ceilings with no in rack sprin klers TECHNICAL DATA ESFR PENDENT SPRINKLERS SIN VK500 K 14 0 Sprinkler Temp Classification Nominal Temperature Rating Fusing Point 2 Maximum Ambient Ceiling Temperature1 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate10 205 F 96 C 150 F 65 C White Approval Chart Vikin...

Страница 2: ...ation Maximum Roof or Ceiling Slope 2 in 12 167 mm m or 9 5 degrees Note If the ceiling is beam and girder or panel construction locate sprinklers in the bays rather than under the beams Sprinkler Position Approved for use only in the pendent position in wet systems FM Global Loss Prevention Data Sheet 2 2 provides the following positioning require ment Install K14 0 ESFR sprinklers with the cente...

Страница 3: ...build up of compound in the sprinkler orifice E With the sprinkler contained in the plastic protective cap install the sprinkler onto the piping by apply ing the special sprinkler wrench shown in Figure 1 to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflect...

Страница 4: ... of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pres sure on the piping 2 Using the special sprinkler wrench remove the old sprinkler and install the new unit Care must be taken to ensure that the replacement sprinkler is the proper model and style with the correct orifice size temperature rating and response characteristics A fully stocked s...