TROUBLESHOOTING GUIDE (con’t)
PROBLEM POSSIBLE CAUSE CORRECTION
2. Refrigerant Valve
a. Initiate manual valve activation
Solenoid Fault,
mode on opposite valve as that
Stuck
Open
suspected. Toggle to evaporator
temp readings associated with
suspected valve to verify it is
closed. If it is open, check
solenoid
electrical
connections
to make sure they are not
crossed. Unplug solenoid to
see if valve closes. If valve
closes, replace solenoid. If valve
does not close, replace valve.
3. Room Temperature
Below Set-Point
a. Instruct customer.
F. 1. “Extremely”
1. Control Set to Display
1. Initiate temperature units
Cold Temperatures
Celsius but Customer
selection mode and select
Displayed (3
°
to 18
°
)
Thought it was
Fahrenheit units of measure.
2. If outside US –
Fahrenheit.
Could be “Extremely”
2. If Outside US – Control
2. Initiate temperature units
Warm Temperatures
Set to Display Fahren-
selection mode and select
Displayed (38
°
to 65
°
)
heit but Customer
Celsius units of measure.
Thought it was Celsius.
G. Lights Stay on in
1. Lights Switched “On”
1. Press & release lights On/Off
Either Wine Storage
100%
key.
Compartments.
2. Fan and Light Switch
2. Check wiring at fan & light
Wiring Crossed
switch, and at control board.
Rewire
if
incorrect.
3. Light Switch
3. Press & release lights On/Off
Malfunction
key, then depress light switch.
Repeat steps. If no effect,
replace
switch.
H. Lights will not
1. Unit in Holiday Mode
1. Press & release unit On/Off key.
Energize in One or
2. Light Burned Out
2. Plug in known good lights. If
All Wine Storage
they work, replace defective
Compartments
lights.
3. Light Switch Discon-
3. Check light switch operation
nected of Malfunction-
and electrical connections.
ing.
Check for 115VAC to and from
Switch. reconnect wires or
Replace switch if defective.
24