background image

Due to the dynamic nature of the product design, the information contained in this document is subject to change without notice. Viking Electronics, and its affiliates and/or subsidiaries
assume no responsibility for errors and omissions contained in this information. Revisions of this document or new editions of it may be issued to incorporate such changes.

DOD# 245

Printed in the U.S.A.

P

P

r

r

o

o

d

d

u

u

c

c

t

t

S

S

u

u

p

p

p

p

o

o

r

r

t

t

L

L

i

i

n

n

e

e

.

.

.

.

.

.

7

7

1

1

5

5

.

.

3

3

8

8

6

6

.

.

8

8

6

6

6

6

6

6

F

F

a

a

x

x

B

B

a

a

c

c

k

k

L

L

i

i

n

n

e

e

.

.

.

.

.

.

7

7

1

1

5

5

.

.

3

3

8

8

6

6

.

.

4

4

3

3

4

4

5

5

ZF303220 Rev 11 

G. Line Verification Test

In accordance to ASME A17.1, the 

LC-6

has the ability to check the incoming telephone line for operability on a daily

basis. The lines running from the 

LC-6

to each of the Viking 

1600A Series

emergency phones will also be tested at

this same time. 

The 

LC-6

verifies the telephone line has loop current, and that each of the emergency phones will answer an incom-

ing call. When a fault is detected, an audible and illuminated visual alarm showing “ELEVATOR COMMUNICATIONS
FAILURE” will display on both the optional 

LM-24D

displays and the optional 

LV-1K

line verification alarm panel. Once

the fault is corrected, the alarm state will clear within two minutes. 

H. LV-1K Line Verification Alarm Panel

The 

LC-6

has a two position terminal block for connection to an optional 

LV-1K

line verification alarm panel. In accord-

ance to ASME A17.1, the 

LV-1K

has “ELEVATOR COMMUNICATIONS FAILURE”  labeled in ¼” high letters, and will

flash a red light and sound an audible signal every 30 seconds when a line verification fault is detected. The 

LV-1K

line

verification alarm panel can service a group of elevators controlled by a Fire Recall switch, and must be located in the
vicinity of that switch and be visible to elevator users. 

I. LM-24 Displays

The 

LC-6

has a two position terminal block for connecting one or two optional Viking model 

LM-24D

displays. The

optional displays provide a visual status of all the phones and the telephone line. When in use, the corresponding LED
will light steady, and a ringing phone will show as a flashing LED.  Emergency phones that are conference bridged into
an existing emergency phone conversation, are displayed as a lit LED that winks once every few seconds. 

The 

LM-24D 

displays will also show the testing status during the line verification tests. When all line verification tests

pass, the “PASSED” LED will light. If a fault is found, the 

LM-24D

displays will flash “ELEVATOR COMMUNICATIONS

FAILURE” along with the line(s) that failed, and an audible signal tone will sound. The volume control on the front of
the 

LM-24D

display can be used to control the volume of the audible signal tone.

The optional 

LM-24D

displays are useful for personnel using the Fire Floor phone, Machine Room phone, and/or Lobby

phones. The 

LC-6

can power one or two 

LM-24D

displays. Displays that are run greater than 400 ft (122 m) away may

need a Viking model 

PS-2

12VDC power supply added for proper operation. With the power supply added, run lengths

of up to 800 ft (244 m) can be achieved.

Fill out the 

LM-24D

Identification Card as shown below:

8

DIAL 1

ELEVATOR 1

DIAL 2

ELEVATOR 2

DIAL 3

ELEVATOR 3

DIAL 4

ELEVATOR 4

DIAL 5

ELEVATOR 5

DIAL 6

ELEVATOR 6

DIAL 7

FIRE FLOOR PHONE

DIAL 8

MACH/LOBBY PHONES

DIAL 9

TELEPHONE LINE

PROGRAMMING

TESTING

PASSED

ELEVATOR

COMMUNICATIONS

FAILURE

Содержание LC--6

Страница 1: ...ation alarm panel can display an Elevator Communications Failure Note Per ASME A17 1 requirements the LC 6 must be used with a battery backup UPS capable of keeping the LC 6 running for up to 4 hours...

Страница 2: ...t be provided to the telephone company The REN is used to determine the number of devices that may be connected to a telephone line Excessive REN s on a telephone line may result in the devices not ri...

Страница 3: ...s emergency phones can be installed to internally communicate with a Fire Floor phone a Machine Room phone and a Lobby phone through the LC 6 The Lobby phone connection is not a separate port but is s...

Страница 4: ...When the LC 6 answers wait for the beep then enter Q followed by the 6 digit security code factory set to 845464 see Programming section B A double beep should then be heard indicating you have entere...

Страница 5: ...the number of times the LC 6 will ring the called device when a transfer is initiated Entering a 0 count will disable the ring counter altogether and the port will continue to ring until answered or t...

Страница 6: ...econds of silence so the LC 6 knows it is a trans fer command and not part of a dialing string Note The internal line does not supply dial tone 2 DIP Switch 2 Line Verification Test When this switch i...

Страница 7: ...a single touch tone 7 or 8 respectively D Fire Floor Phone When the Fire Floor phone goes off hook the LC 6 will send a single beep The user can then enter a touch tone 1 to 6 to call emergency phone...

Страница 8: ...cation fault is detected The LV 1K line verification alarm panel can service a group of elevators controlled by a Fire Recall switch and must be located in the vicinity of that switch and be visible t...

Отзывы: