TECHNICAL DATA

January 6, 2012

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Preaction 328d

2” MoDEL G-2000P PrEACTIoN 

wITH ELECTrIC rELEAsE

NoTE: 

�iking recommends tank-mounted air com�ressors �or Double Interlock Electric/Pneu-Lectric Release Preaction Systems.

2. Nitrogen Cylinder Gas Su��ly (See Figure 1) 

Nitrogen may be used in �lace o� air com�ressors. Nitrogen is su��lied in �ressurized cylinders in various sizes and �ressures. 

Some o� the most common are 122 Cu. Ft. at 1,900 PSI (3,455 L at 131 bar), 225 Cu. Ft. at 2,100 PSI (6,372 L at 145 bar), and 

280 Cu. Ft. at 2,300 PSI (7,930 L at 159 bar). 

When nitrogen cylinders are used as a �rimary air su��ly, s�are cylinders should be �urnished and located at the valve location. 

To determine the a��roximate amount o� nitrogen to be �urnished, the �ollowing �ormula may be used: 

S�ecial attention must be given to systems em�loying a bottled-gas su��ly. Because only a limited amount o� gas is available, 

small leaks, which normally would go unnoticed in systems being su��lied by mechanical com�ressors, can become critical to 

the system’s overall �er�ormance. I� the system is to �unction at tem�eratures as low as -40 °F (-40 °C), and, i� bottled nitrogen 

is the gas su��ly, the system is �articularly susce�tible to leakage, and s�ecial care should be taken to ensure against leaks 

throughout the entire system.

C.   Air supply Installation:

1.  Install the required air su��ly as described in section 4.B. The size o� the com�ressor and amount o� air required should be 

determined in accordance with Tables 1 - 3. The air or nitrogen su��ly to the �reaction system must be clean, dry, and oil �ree.

2.  Automatic air su��lies must be regulated, restricted, and �rom a continuous source. A �iking Air Maintenance Device should 

be installed on each system equi��ed with a tank-mounted com�ressor, �lant air, or nitrogen. For com�ressors with a ca�acity 

less than 5.5 �t

3

/min at 10 PSI (0.154 m

(0.154 m

3

/min at 0.69 bar), NFPA 13 does not require an air maintenance device. In addition,

 NFPA 13 does not require an air maintenance device. In addition, 

an air maintenance device should not be used with riser mounted com�ressors as this can lead to com�ressor “short cycling”. 

�iking recommends that a tank-mounted com�ressor with air maintenance device be used. This can become critical when

This can become critical when 

accelerators are installed on the system. 

D.   Pressure switch wiring:

Wire the Alarm Pressure Switch (PS10) and Air Su�ervisory Switch (PS40), and adjust �ressure settings as shown in Figures 2 - 4.

Figure 4 - Pressure Adjustment

Figure 2 - Alarm Pressure switch wiring

(Alarm Pressure Switch should be set to 5 PSI (0.34 bar)

FIELD ADJUsTMENTs: 

Alarm Pressure switch:

 The o�erating �oint o� the switch can be 

adjusted to any �oint between 4 PSI (0.27 bar) and 8 PSI (0.55 bar) 

by turning the adjustment knob(s) clockwise to raise the actuation 

�oint or counter-clockwise to lower the actuation �oint.

Air supervisory switch: 

The o�erating �oint o� the switches can 

be  adjusted  to  any  �oint  between  10  PSI  (0.7  bar)  and  60  PSI 

(4.1 bar) by turning the adjustment knob(s) clockwise to raise the 

actuation �oint or counter-clockwise to lower the actuation �oint. 

The high and low switches are adjusted inde�endently.

Metric Units

�c = 

�s x P

where:

�c = �olume o� Cylinder (L)

 P = Required Nitrogen Pressure (bar)

 � = �olume o� System (L)

108

Figure 3 - Air supervisory switch wiring

single Interlock

Double Interlock

English Units

�c = 

�s x P

where:

�c = �olume o� Cylinder (�t

3

)

 P = Required Nitrogen Pressure (PSI)

 � = �olume o� System (gal)

100

Содержание G-2000P

Страница 1: ...a sprinkler operates B Viking Supervised Double Interlocked Electric Pneu Lectric Release Preaction Systems Utilizing the Viking G 2000P Valve The system piping is pressurized with air or nitrogen to serve both as a means of supervising the integrity of the piping network and as one portion of the system release operation This feature serves to prevent undetected leaks on the system piping net wor...

Страница 2: ... by NFPA 13 for single interlock preaction systems maintaining higher air pressure within the system will assist maintenance personnel in finding and isolating inadvertent or accidental leaks within the system quickly NFPA 13 requires that the air supply be capable of filling the entire sprinkler system to its required air pressure within 30 minutes A common method of sizing an air compressor is t...

Страница 3: ...vcs vikingcorp com Preaction 328c Figure 1 Air Supply Options Tank Mounted Air Riser Mounted Air Riser Mounted Air Compressor Tank Mounted Air Compressor Pressure Relief Valve Viking Model D 2 Air Maintenance Device Warning Do not allow pressures in excess of 175 psi from reaching the AMD Nitrogen Regulator Pressure Relief Valve Nitrogen Bottle Nitrogen Air Supply Option Not provided by Viking Com...

Страница 4: ...air or nitrogen supply to the preaction system must be clean dry and oil free 2 Automatic air supplies must be regulated restricted and from a continuous source A Viking Air Maintenance Device should be installed on each system equipped with a tank mounted compressor plant air or nitrogen For compressors with a capacity less than 5 5 ft3 min at 10 PSI 0 154 m3 min at 0 69 bar NFPA 13 does not requ...

Страница 5: ...ol valve Wait until water exits the emergency release valve and then CLOSE the emergency release valve 5 Close the prime valve and observe the prime pressure gauge for at least 15 seconds If the gauge pressure drops check the prime line and drip check make sure the leak is fixed before proceeding to the next steps Finally RE OPEN the priming valve and verify required prime pressure has been establ...

Страница 6: ...n A In the Set position Air pressure is introduced into the sprinkler piping for supervisory purposes only for single interlock systems For double interlock systems air pressure is used for supervisory purposes and as one of the two initiation actions of the cross zoned solenoid Prime water is routed to the normally closed solenoid valve and to the prime chamber When prime water enters the prime c...

Страница 7: ...Single Interlock System B Activation of Release System Single Interlock System When the detection system operates the normally closed solenoid valve is powered open Prime water is drained from the prime chamber causing the G 2000P Valve to open filling the sprinkler piping with water Water from the intermediate chamber of the G 2000P Valve pressurizes the sensing end of the PORV causing the PORV t...

Страница 8: ... causing an alarm to activate When a sprinkler operates air pressure escapes from the sprinkler piping The air supervisory switch activates the second initiating circuit in release control panel When BOTH initiating circuits have been activated the release control panel energizes solenoid valve open With the solenoid valve open prime water is drained from the prime chamber causing the G 2000P Valv...

Страница 9: ...nded pressure 6 Reset the system release control panel The supervisory alarms should stop When testing is complete return the system to service following steps 1 through 8 below B Full Flow Trip Test Refer to Figure 5 Performance of a trip test is recommended annually during warm weather Consider coordinating this test with operation testing of the detectors Caution Performance of this test will c...

Страница 10: ...ts of the coupling 6 remove the coupling 6 from the valve body 1 3 Inspect the coupling 6 and O rings 5 Replace if necessary using the instructions in O Ring Replacement Bulletin F_120611 F Removing Replacing the Prime Chamber Assembly Refer to Figure 11 1 The prime chamber assembly 4 is now held in place by two flanges on the outside diameter of the assembly Slide the prime chamber assembly 4 tow...

Страница 11: ...s vikingcorp com Preaction 328k Figure 8 16187 1 Assembly Figure 9 Optional Accessories Accessories 08055 Model E 1 Accelerator 14800 Model LD 1 Anti Column Device 16211 Drain Manifold Part Number 16187 1 1 Model G 2000P Valve 1 Model G 2000P Electric Release Trim Includes NC Solenoid 1 10 Section of Schedule 10 Pipe and Coupling 1 Air Pressure Supervisory Switch PS40 2A 1 Alarm Pressure Switch PS...

Страница 12: ...tion 210 N Industrial Park Drive Hastings MI 49058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Preaction 328l 2 Model G 2000P Preaction with Electric release Figure 10 Installation Dimensions ...

Страница 13: ... 304 Stainless Steel Bronze Alloy 1 5 O Rings EPDM and Nitrile 2 or 3 6 16062 Coupling UNS S17400 Stainless Steel 1 7 15932 Check Diaphragm EPDM 1 8 08091 3 8 16 x 1 HHS UNS S30400 Stainless Steel 8 9 Cover 65 45 12 Ductile Iron 1 10 Data Plate Aluminum 2 11 Tack Alloy Carbon Steel 4 Replacement part is not available Indicates part is available only in a Sub Assembly as indicated below Sub Assembl...

Отзывы: