4.  iNStaLLatiON

Viking Flexible Sprinkler Connection Assemblies are manufactured and tested to meet the latest rigid requirements of the approv-

ing agencies. They are designed and tested to be installed in accordance with the Approved and Listed installation instructions 

as provided with the product and the recognized installation standards. Deviations from these standards or any alterations to the 

support system or sprinkler after leaving the factory including, but not limited to painting, plating, coating or modification may render 

the sprinkler inoperative or the support system non-compliant, automatically nullifying the approvals and any guarantee made by 

The Viking Corporation. 

Flexi�le Sprinkler Connection with Bracket System assem�ly: (See figures 1 - 4)

Viking Flexible Sprinkler Connections are offered pre-assembled from the factory with the center bracket and inside/outside brack-

ets attached to the square bar.  

SKiP tO StEP tWO

, unless the standard factory assembled product is not provided.

Step 1- Slide the square bar into the center bracket assembly.  Attach the two inside brackets to the square bar with two M6 x 25mm wing bolt. 

Tighten the wing bolts to 30 in-lbs. (1/4 turn past hand tight).  Loosely attach the two outside brackets to the inside brackets with two M6 x 25 

mm wing bolts.

Step 2

- Install the bracket assembly onto the main tee bars of the ceiling so that the main tee is between the inside bracket and 

the outside bracket. Install the outlet extension nipple into the center bracket assembly. Locate the bracket assembly to the desired 

position of the sprinkler. Tighten the wing bolt of the center bracket to 75 in. lbs. (1/2 turn past hand tight).  Tighten the wing bolts 

of the side brackets to 30 in-lbs. (3/4 turn past hand tight).

Step 3- 

Install the 1” inlet nipple into the sprinkler branch line pipe. Connect the flexible hose to the inlet nipple with a torque of 

75 in-lbs. (1/2 turn past hand tight). Connect the flexible hose to the outlet extension nipple with a large smooth bend having a 

minimum radius of 12” in (305 mm). Tighten the flexible hose to the outlet extension nipple with 75 in-lbs (1/2 turn past hand tight). 

Multiple bends are permissible when done in accordance with Table 2.

Step 4- 

Attach the sprinkler to the outlet extension nipple. Use a wrench on the extension nipple and the proper sprinkler wrench 

on the sprinkler when tightening.

Step 5- 

Installation is complete.  See Figure 2 for acceptable bends.

The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction prior 

to installation. 

Keep sprinklers with protective shields or caps contained within the shields or caps during installation and testing, and 

any time the sprinkler is shipped or handled. 

For concealed style sprinklers, the cover plate assembly can now be installed onto the sprinkler.

a. Remove the cover from the protective box, taking care not to damage the cover plate assembly.

b. From below the ceiling, gently place the base of the cover assembly over the sprinkler protruding through the ceiling opening.

c. Push the cover plate assembly onto the sprinkler until the unfinished brass flange of the cover plate base touches the ceiling.

d. Available cover plate adjustment is ½” (12.7 mm) +/- 1/4” (6.4 mm).

For frame style sprinklers with the Model E-1 or E-2 Escutcheon, or with the Model F-1 Escutcheon, press on or thread on the outer 

escutcheon cup until the flanges touch the surface of the ceiling.

a. With the E-1 or E-2 Escutcheon, the maximum recess is ½” (12.7 mm). The face of the escutcheon adapter may extend up 

to 11/32” (8.7 mm) beyond the edge of the escutcheon cup, resulting in 27/32” (21.4 mm) total adjustment range.

If it is necessary to remove the entire sprinkler unit, the system must be taken out of service. See section 6. INSPECTIONS, TESTS 

AND MAINTENANCE and follow all warnings and instructions. 

5.  OPEratiON

Refer to the sprinkler technical data page for the sprinkler model used with the Flexible Sprinkler Connection Assembly. 

remove plastic protective sprinkler caps or �ul� shields aFtEr the ceiling finish work is completed where the sprin-

kler is installed and there no longer is a potential for mechanical damage to the sprinkler operating elements. 

To 

remove the bulb shields, simply pull the ends of the shields apart where they are snapped together. To remove caps from 

frame style sprinklers, turn the caps slightly and pull them off the sprinklers. 

SPriNKLEr CaPS Or BULB SHiELDS MUSt BE 

rEMOVED FrOM SPriNKLErS BEFOrE PLaCiNG tHE SYStEM iN SErViCE! 

Retain a protective cap or shield in the 

spare sprinkler cabinet.

Содержание FSC-28B

Страница 1: ...ping system and the outlet sprinkler fitting is made with a slip nut and seal design that allows assembly after forming the flex hose to proper installation shape and the inlet and outlet end connections are securely in place This prevents twisting of the flex sprinkler connection during installation and provides a secure leak tight assembly The Viking Model FSC 28B Braided Flexible Sprinkler Conn...

Страница 2: ... Nut SS41 ASTM A283 D Steel with zinc plating Support Brackets all SS41 ASTM A572 Steel with zinc plating Support Bar SS41 ASTM A283 D Steel with zinc plating Insulating Collar Nylon 66 Ordering Information Also refer to the current Viking price list The Following Model FSC 28B Flexible Sprinkler Connections are Available as Stock Assemblies Part No 18731 10 1 NPT x 1 2 NPT x 39 3 8 1000mm length ...

Страница 3: ...the flexible hose to the outlet extension nipple with 75 in lbs 1 2 turn past hand tight Multiple bends are permissible when done in accordance with Table 2 Step 4 Attach the sprinkler to the outlet extension nipple Use a wrench on the extension nipple and the proper sprinkler wrench on the sprinkler when tightening Step 5 Installation is complete See Figure 2 for acceptable bends The use of certa...

Страница 4: ...200mm Spacing 18469 Side Bracket Assembly Includes Side Bracket 18287 and 14401 18286 Center Bracket Assembly Includes Center Bracket 18292 and 18293 18287 Wing Bolt M6 x 1 25mm 18727 Outlet Reducing Nipple 1 2 NPT 18728 Outlet Reducing Nipple 3 4 NPT 18292 Wing Bolt M6 x 2 3 4 70mm 18293 Retaining O RIng 14386 EPDM Seal for 28 mm hose assembly 14378 Inlet Nipple 1 NPT The Following Kits are Avail...

Страница 5: ...t must be followed A Sprinklers must be inspected on a regular basis for corrosion mechanical damage obstructions paint etc The frequency of inspections may vary due to corrosive atmospheres water supplies and activity around the device B Sprinklers that have been field painted or mechanically damaged must be replaced immediately Sprinklers showing signs of corrosion shall be tested and or replace...

Страница 6: ...rporation 210 N Industrial Park Drive Hastings MI 49058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Form No F_012213 Rev 14 1 Page of 8 Figure 1 Installation Schematic Figure 2 Bends Acceptable Not Acceptable Not Acceptable ...

Страница 7: ...es 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Form No F_012213 Rev 14 1 Page of 8 Figure 3 Flexible Sprinkler Connection Support System No Description 1 Top Wing Bolt M6 X P1 x 1in 25mm Long 2 Square Bar 3 Side Wing Bolt M6 X P1 X 1in 25mm Long 4 Outside Bracket 5 Inside Bracket 6 Center Bracket Assembly 7 Center Bracket Wing Bolt M6 X P1 X 2 3 4in 70mm Long ...

Страница 8: ...ail techsvcs vikingcorp com Form No F_012213 Rev 14 1 Page of 8 Figure 5 Flexible Sprinkler Connection Figure 4 Flexible Sprinkler Connection Installed With Bracket System Assembly 1 NPT Inlet x 1 2 NPT Straight Outlet Braided 1 NPT Inlet x 3 4 NPT Straight Outlet Braided Figure 6 Flexible Sprinkler Connection 1 NPT Inlet x 1 2 NPT 90º Outlet Braided 1 NPT Inlet x 3 4 NPT 90º Outlet Braided Remove...

Отзывы: