J. Starting the CTG-1A Operation
K. Clearing the Alert Tone Memory
L. DIP Switch Settings
Momentarily press the
Mode
button until the
Events
LED lights. Simultaneously press the
Single
and
Cancel
buttons, release both and repeat. Pressing both buttons the second time will start the
clearing process. When the clear process has finished, a long tone will be heard. If a second
schedule is used, it will need to be cleared seperately with dip switch 3 on.
Switch
Position
Description
1
OFF
Program Bong alert tones *
1
ON
Program Buzzer alert tones
2
OFF
Send Tones mode *
2
ON
Timed Relay mode
3
OFF
Select Schedule 1 *
3
ON
Select Schedule 2
4
OFF
Use Standard Time *
4
ON
Use Daylight Saving Time
5
OFF
50 Hz power line frequency
5
ON
60 Hz power line frequency *
When finished programming, press the
MODE
button until the
RUN
indicator lights. In the run mode,
all buttons except the
MODE
button are disabled and the current time will be displayed with the
colon flashing
.
Internal View of the CTG-1A
ON
OFF
C
LED1
C
LED6
C
LED2
C
LED3
C
LED5
C
LED4
1
3
4
2
ON
5
C
LED7
*
Factory Setting
I. Activating Contact Closure Alarm Tones
To activate different sounds, short the
corresponding pins with a dry contact closure
as shown right (see
Installation
).
Note:
The evacuation sound and siren will
be repeated continuously, as long as the
closures are maintained.
Sound
Short Pins...
Doorbell (Ding Dong)
...9 to 12
Siren (Yelp)
...10 to 12
Evacuation Sound (Slow Whoop)
...11 to 12
H. Adjusting Output Volume
Step 1.
Use a jumper wire to short pins
10
and
12
together. The siren sound will then play.
Step 2.
Adjust the output volume control (see
Features Overview
) until the desired volume is
achieved.
Step 3.
Remove the jumper between pins 10 and 12.