SPRINKLER GENERAL CARE, 

INSTALLATION, AND 

MAINTENANCE GUIDE

TECHNICAL DATA

Page 1 of 4

Form No. F_080614       18.10.11     Rev 16.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visit the Viking website for the latest edition of this technical data page.

1.  DESCRIPTION - 

STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRY SPRINKLERS

Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available 

styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending 

on the particular sprinkler model selected. 
Viking sprinklers are available with various finishes, temperature ratings, responses, and K-Factors to meet design requirements†. 

Used in conjunction with one of the corrosion-resistant coatings (for frame style sprinklers), the units provide protection against 

many corrosive environments. In addition, the special Polyester or 

37)(

 coatings can be used in decorative applications where 

colors are desired.

† Refer to the sprinkler technical data page for available styles, finishes, temperature ratings, responses, and nominal K-Factors for specific sprinkler models. 

2.  LISTINGS AND APPROVALS

Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or approval agency listings.

3.  TECHNICAL DATA

Specifications:

Refer to the appropriate sprinkler technical data sheet.

Material Standards:

Refer to the appropriate sprinkler technical data sheet.

4.  INSTALLATION

NOTE: Take care not to over-tighten the sprinkler and/or damage its operating parts! 

Maximum Torque: 

 

1/2” NPT:   14 ft-lbs. (19.0 N-m)        
3/4” NPT:   20 ft-lbs. (27.1 N-m)         
1” NPT:   30 ft-lbs. (40.7 N-m)

A. Care and Handling (also refer to Bulletin - Care and Handling of Sprinklers, Form No. F_091699.)

Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install 

sprinklers that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature al-

lowed (refer to the temperature chart on the sprinkler technical data page). Never install any glass-bulb sprinkler if the bulb is 

cracked or if there is a loss of liquid from the bulb. A small air bubble should be present in the glass bulb. Any sprinkler with a 

loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately. (Note: Installing glass bulb 

sprinklers in direct sunlight (ultraviolet light) may affect the color of the dye used to color code the bulb. This color change does 

not affect the integrity of the bulb.)

Sprinklers must be protected from mechanical damage during storage, transport, handling, and after installation. Sprinklers subject 

to mechanical damage must be protected with an approved sprinkler guard. 

Use only sprinklers listed as corrosion resistant when subject to corrosive environments. When installing corrosion-resistant sprin-

klers, take care not to damage the corrosion-resistant coating. Use only the special wrench designed for installing coated or 

recessed Viking sprinklers (any other wrench may damage the unit).

Concealed sprinklers must be installed in neutral or negative pressure plenums only!

 

Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they could be exposed to 

temperatures exceeding the maximum recommended ambient temperature for the temperature rating used.

Wet pipe systems must be provided with adequate heat. Sprinklers supplied from dry systems in areas subject to freezing must 

be listed dry sprinklers, upright, or horizontal sidewall sprinklers installed so that water is not trapped. For dry systems, pendent 

sprinklers and sidewall sprinklers installed on return bends are permitted, where the sprinklers, return bend, and branch line 

piping are in an area maintained at or above 40 °F (4 °C).

B. Installation Instructions - Standard Spray Sprinklers

Viking sprinklers are manufactured and tested to meet the rigid requirements of approving agencies. They are designed to be 

installed in accordance with recognized installation standards. Deviation from the standards or any alteration to sprinklers or cover 

plate assemblies after they leave the factory including, but not limited to: painting, plating, coating, or modification, may render them 

inoperative and will automatically nullify the approvals and any guarantee made by The Viking Corporation.

Replaces Form No. F_080614 Rev 16.1

(Added P65 Warning.)

Содержание 23874

Страница 1: ...5 bar Rated to 175 psi 12 bar water working pressure Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 NPT 15 mm BSPT Nominal K factor 8 0 U S 115 metric Glass bulb fluid temperature...

Страница 2: ...ature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A Installer Wrench Part No 22055 available since 2017 B Cabinet Wrench Part No 20901M B available since 2017 C Recessed Socket Wrench...

Страница 3: ...55 F 68 C 175 F 79 C and 200 F 93 C C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C D 155 F 68 C 175 F 79 C and 200 F 93 C Approved Finishes 1 Brass Chrome White Polyester 3 4 Black Polyester 3 4 a...

Страница 4: ...applicable DESIGN CRITERIA FM FM Approval Requirements The Viking VK3522 Quick Response Pendent Sprinkler is FM Approved as quick response Non Storage Pendent sprinkler as indicated in the FM Approval...

Страница 5: ...3 Recessed Installation with Recessed Socket Wrench A 1 2 ratchet is required not available from Viking Figure 4 Recessed Installation with standard Installer s Wrench 2 Carefully slide the wrench sid...

Страница 6: ...3 Thread On Recessed Escutcheon E 3 and NP 3 Outer rings have larger diameters Max 1 7 16 37 mm Max 1 3 4 44 mm Min 13 16 21 mm Min 15 16 24 mm Ceiling opening size Minimum 2 5 16 59 mm Maximum 2 1 2...

Страница 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 11: ...readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification...

Страница 12: ...y intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler...

Страница 13: ...ENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking C...

Страница 14: ...e sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any s...

Страница 15: ...ctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements...

Страница 16: ...her To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVI...

Страница 17: ...rior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service d...

Страница 18: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Страница 19: ...render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERA...