CARE AND HANDLING 

OF SPRINKLERS

Page 3 of 4

Form No. F_091699     18.10.11    Rev 16.1.P65

GENERAL HANDLING AND STORAGE INSTRUCTIONS:

• 

Do not store in temperatures exceeding 100 °F (38 °C). Avoid direct sunlight and confined areas subject to heat.

• 

Protect sprinklers and cover assemblies during storage, transport, handling, and after installation. 

-- Use original shipping containers. 

-- Do not place sprinklers or cover assemblies loose in boxes, bins, or buckets.

• 

Keep the sprinkler bodies covered with the protective sprinkler cap any time the sprinklers are shipped or handled, during testing of the system, and 

while ceiling finish work is being completed.

• 

Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. 

NOTE:

 The protective cap is 

temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed. 

• 

Do not over-tighten the sprinklers into fittings during installation.

• 

Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation.

• 

Do not attempt to remove drywall, paint, etc., from the sprinklers.

• 

Remove the plastic protective cap from the sprinkler before attaching the cover plate assembly. 

PROTECTIVE CAPS  MUST BE REMOVED FROM 

SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! 

Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data 

pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.

vikinggroupinc.com.

 Concealed Sprinkler and Adapter 

Assembly with Protective Cap

CAUTION: CONCEALED COVER ASSEMBLIES ARE FRAGILE!

TO ASSURE SATISFACTORY PERFORMANCE OF THE PRODUCT, HANDLE WITH CARE

.

 Cover Plate Assembly 

(Pendent Cover 12381 shown)

 Concealed Sprinkler and Adapter 

Assembly (Protective Cap Removed)

Содержание 08687

Страница 1: ...4 5 bar Factory tested hydrostatically to 500 psi 34 5 bar Thread size 3 4 20 mm NPT Nominal K Factor 11 2 U S 161 3 metric Metric K factor measurement shown is in Bar When pressure is measured in kPa...

Страница 2: ...bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern...

Страница 3: ...rinkler Finishes Brass Chrome White Polyester3 Black Polyester3 and ENT Corrosion Resistant Coatings4 ENT Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Ot...

Страница 4: ...min 84 Bar D1 D2 16 ft x 16 ft 4 9 m x 4 9 m 256 ft2 23 8 m2 30 gpm 7 2 psi 113 6 L min 50 Bar B1 E2 18 ft x 18 ft 5 5 m x 5 5 m 324 ft2 30 1 m2 33 gpm 8 7 psi 124 9 L min 60 Bar B1 E2 20 ft x 20 ft...

Страница 5: ...ly cULus Listed for Ordinary Hazard Occupancies For non combustible obstructed construction within trusses or bar joists having non combustible web members greater than 1 25 4 mm when applying the 4 t...

Страница 6: ...When using 10 6 x 13 0 sprinkler spacing provide the Minimum Water Supply Requirement listed in the chart for 14 0 x 14 0 spacing For areas of coverage smaller than shown use the Minimum Water Supply...

Страница 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Отзывы: