STANDARD/QUICK RESPONSE
EXTENDED COVERAGE
UPRIGHT SPRINKLER
VK532 (K11.2)
TECHNICAL DATA
Page 3 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Form No. F_053114 19.10.14 Rev 19.1
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
1
Maximum Ambient
Ceiling Temperature
2
Bulb Color
Ordinary
135 °F (57 °C)
100 °F (38 °C)
Orange
Ordinary
155 °F (68 °C)
100 °F (38 °C)
Red
Intermediate
175 °F (79 °C)
150 °F (65 °C)
Yellow
Intermediate
200 °F (93 °C)
150 °F (65 °C)
Green
High
286 °F (141 °C)
225 °F (107 °C)
Blue
Sprinkler Finishes:
Brass, Chrome, White Polyester
3
, Black Polyester
3
, and ENT
Corrosion-Resistant Coatings
4
:
ENT
Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester.
4
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For ENT sprinklers, all exposed surfaces and the waterway are coated, but note that the spring
is exposed.