ELECTRICAL SPECIFICATIONS
GENERAL
NOTICE: All spa electrical wiring must be performed by
a qualified, licensed electrician in order to meet NEC
(National Electrical Code) state and local codes.
1.
The lines carrying power to the spa must be dedicated to the
spa and should not be shared with any other appliance(s).
2.
All electrical wiring lines must originate from the electrical
panel and terminate, hard wired, into the electrical wiring
compartment. The use of extension cords or improper plug
type termination is expressly prohibited and voids the warranty.
3.
Do not use aluminum wiring.
Use only copper conductive
wiring.
4.
Wire gauge must be in accordance with NEC
requirements
for the distance from current source to spa and
the current rating as stated on the ID label that is attached to
the equipment control enclosure.
5.
All wiring installed in conduit must be approved for usage
by state and local codes. The conduit must terminate at the
electrical access compartment either from the bottom of the
spa or through a hole in the side panel of the spa.
NOTE
: The Viking I, Viking II, Aurora I and Eclipse models are avail-
able with a 110v option. The Viking III, Aurora II, Aurora III,
Supreme, Royale, Royale ETS, Legacy, Legend, Heritage models are
220v only systems.