The cabinet must be supplied with a dedicated mains feed direct from a
main switchboard (refer AS/NZS 3000). A 10A circuit breaker is required
for a system with the standard MX1 5A PSU.
The termination of the mains cable into the mains outlet inside the
MX1
and at the distribution board must be done by a suitably qualified
electrician. If the mains cable is routed inside the cabinet, the outer
sheath of the cable must be maintained unbroken until after the cable
enters the mains outlet. The PSU module power lead plugs into the
mains outlet.
Wherever possible the mains cable should be routed through the back of
the cabinet using the gearplate slot and cabinet knockout inside the
mains outlet. Alternatively, route the mains cable through the bottom left-
hand side of the cabinet
– this reduces the possibility of water ingress
and provides an acceptably short wiring path. The mains cable should
be routed up the left-hand side of the cabinet and terminated in the mains
outlet on the gearplate. This is to minimise electrical interference
between the mains supply and the other circuits connected to the
electronics.
A mains socket, mounting block and mounting hardware (two x M4 x 10
screws) are supplied fitted. Remove and cut the mounting block to allow
cable entry and fit to the gearplate as per Figure 11.4. Connect the
incoming mains into the mains socket (ensure correct wiring) and mains
earth wire into the earth terminal on the gearplate, then re-fit the switch
plate using the supplied screws. Do not remove the earth wire between
the gearplate and the GPO.
Mains Wiring
Mains Wiring
– 8U / 15U Cabinet
Содержание MX1-Au
Страница 104: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 8 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 9 14 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 160: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 11 34 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 182: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 12 22 THIS PAGE INTENTIONALLY LEFT BLANK...