background image

 

L:\Product Documentation\Manuals\Doc\MEW00442.doc

 

 Operating 

Instructions 

MEW00442 

Revision - 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fire Alarm System EBL512 

V1.44.x 

 

Author: 

Jan Pettersson 

Date: 

2003-09-09 

Rev. date: 

 

Checked by:  Mikael Östergren 

S-class:  Public 

Rev. by: 

 

Approved by:  Rutger Pålsson 

 

Number of pages:  111 

Summary of Contents for EBL512

Page 1: ...oc MEW00442 doc Operating Instructions MEW00442 Revision Fire Alarm System EBL512 V1 44 x Author Jan Pettersson Date 2003 09 09 Rev date Checked by Mikael stergren S class Public Rev by Approved by Ru...

Page 2: ...This page has deliberately been left blank...

Page 3: ...splay unit_______________________________________ 7 2 7 COM loop ________________________________________ 7 2 8 BS4 loop _________________________________________ 7 2 9 Control Unit C U C I E ________...

Page 4: ...__________ 26 12 2 Technical number for BS4 loop units __________________ 27 12 3 Presentation number _______________________________ 28 13 Alarm types _______________________________ 29 13 1 Pre alar...

Page 5: ...H2 B4 ____________________________ 64 24 5 Re enable zone address H2 B5 _____________________ 65 24 6 Re enable control output H2 B6 _____________________ 66 24 7 Re enable non reset zone address H2 B...

Page 6: ..._________ 95 30 2 Disable or re enable outputs for routing equipment H8 S1 96 30 3 Disconnect COM loop H8 S2 ______________________ 97 30 4 Re connect Loop H8 S3 ___________________________ 98 30 5 Ac...

Page 7: ...Products Consists of one or more parts HW according to a Product Parts List A product has a type number e g 1548 an article number often the type no and sometimes is a country code added e g 1548SE a...

Page 8: ...dressable an address setting tool is used for detector types 3xxx and a DIL switch in the ASB see below for detectors 2xxx An analog detector has to be plugged in an ASB 2 2 4 Analog Sensor Base ASB A...

Page 9: ...line conventional zone line intended for one or more conventional alarm points End of line resistor in the last alarm point 2 3 Output unit Addressable unit with programmable control outputs To be co...

Page 10: ...System Several control units connected via a TLON network co operating control units 2 13 Network TLON LonWorks Echelon Node TLON Conn board Gateway Channel Router Repeater Brief explanations to the w...

Page 11: ...ms fault messages etc Normally alphanumeric characters and backlight 2 17 Door open Key switch In most EBL512 configurations there is a door switch which is activated when the control unit door is ope...

Page 12: ...s to all information EBL512 is designed according to the European standards EN 54 part 2 and 4 3 1 1 Expansion boards In the control unit c i e it is possible to mount up to six expansion boards The f...

Page 13: ...mming PC SW Win512 and commissioning of the control unit system is very easy Start with one control unit and then when required add more units The TLON network makes it possible to install the control...

Page 14: ...as ahead of the FBP part see Figure 1 When the door is open you fully see the front adhesive the Fire Brigade Panel FBP and Control Panel CP see Figure 2 Figure 2 Front adhesive FBP upper black part a...

Page 15: ...e if programmed Required fire brigade personnel manoeuvres can be performed from the FBP The CP is used to communicate with the system e g for commissioning monthly tests or maintenance The CP has sev...

Page 16: ...it s normal trigger condition is met or when a programmable input is activated e g L5 will be turned on when an input is activated by a TX output Push buttons on the Fire Brigade Panel FBP Push butto...

Page 17: ...lts not acknowledged are generated in the system 2 Output s for fault tx routing equipment is are activated L16 Key switch 9 yellow see chapter Door open Key switch see page 25 The control unit door i...

Page 18: ...function 0 9 Numeric keys for the figures 0 9 Left right keys to move the cursor in a menu Up down keys to scroll between the menus C Clear deletes just written data A Accept a menu and accept input o...

Page 19: ...vice commissioning the system etc Access level 5 Access code for level 5 is required Service commissioning engineer Code to connect a PC i e for Win512 The access codes can be changed To change a code...

Page 20: ...Present system status on display and printer U1 Disablement U2 Disablement by time channel U3 Show open doors 16 U4 Activated 2 zone address dependent zone address U5 Show sensors week average values...

Page 21: ...in access level 2 plus the following H8 Maintenance S1 Disable or re enable outputs for routing equipment Fire brigade tx Fault tx S2 Disconnect COM loop S3 Re connect Loop S4 Acknowledge service sign...

Page 22: ...out site specific data A5 Display current consumption in unit A6 Display current consumption on COM BS4 loop A7 Display statistics for COM loop A8 Select unit on COM loop and BS4 loop to use for trigg...

Page 23: ...0442 Rev Operating Instructions EBL512 V1 44 x 21 7 Normal operation When the control unit system is in normal operation i e no fire alarm no fault no disablement no service signal not in test mode an...

Page 24: ...more The LEDs will be turned OFF indicating a normal state 8 2 Silence during a fire alarm If the push button Silence is pushed during a fire alarm the following will happen LEDs Fire and Alarms queue...

Page 25: ...on Alarm device off Via menu H2 B9 all outputs programmed for sounders type 3 alarm devices can be turned OFF disabled In case of a fire the sounders will remain turned OFF not sound They will be turn...

Page 26: ...H2 B8 all control output types 0 control general 1 fire ventilation 2 extinguishing system21 can be collective turned OFF disabled They will be turned OFF disabled until they are turned ON re enabled...

Page 27: ...ED Key switch is indicating door open in the same control unit as the LED is situated Indication open door external FBP In both cases above could be chosen if an open door in one or more external FBPs...

Page 28: ...x 26 12 Technical number Presentation number 12 1 Technical number for COM loop units The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also...

Page 29: ...BS4 loops Technical number is also used to identify which unit has generated a fault NOTE In the technical number for unit connected to a BS4 loop the board number 4 Autronica interface board 0 the b...

Page 30: ...r is shown in the FBP display s 23 to identify the point zone generating fire alarm It is also used to disable re enable fire alarm points zones and in control conditions expressions to activate the p...

Page 31: ...e used when early alarm actions are required but no activation of alarm devices routing equipment etc e g computer soft power off In case of a pre alarm the following will happen The buzzer in the con...

Page 32: ...ne 123 address 45 If more than one fire alarm are generated28 the LEDs Alarms queued L2 are blinking To scroll through the alarms use push button Scroll P1 Example more than one fire alarm The alarms...

Page 33: ...point is in alarm status see chapter Activated 2 zone address dependent H4 U4 page 74 13 3 Heavy smoke alarm A sensor generates heavy smoke alarm for a higher offset level 31 than the offset level for...

Page 34: ...abinet alarm xx control unit number This alarm will also generate a fault message indicated by LED Fault L8 Fault tx output s will not be activated 14 2 Key cabinet opened in conjunction with a fire a...

Page 35: ...o be reset the same way as the first one NOTE If the sounders have been silenced LED Silence L7 is lit Push Silence P2 to return to normal state LED Silence will be turned OFF When all fire alarms are...

Page 36: ...ay as a normal fault see chapter Fault acknowledge page 47 When the key cabinet fault is acknowledged the LED Fault L8 will be turned OFF if the key cabinet is closed and if there are no other faults...

Page 37: ...fault has been corrected before it has been acknowledged the text Serviced is added after the time 37 Faults and disablements are indicated by a 2 sec beep when an open control unit door is being clo...

Page 38: ...eck programming Win512 Fault on connected unit s FAULT 1583 Extinguishing system CU xx 1583 German FBP interface board Fault in the extinguishing system equipment connected to the 1583 board in contro...

Page 39: ...84 Autronica interface board Fault on the 1584 board FAULT Charging control unit xx Also indicated by LED Fault Power supply Loss of mains i e no 230 V AC the fault is activated after five hours the t...

Page 40: ...hen short circuit isolators are used communication in both directions A double break will give the message FAULT No reply NOTE Communication in both directions lasts for about ten minutes when a new a...

Page 41: ...LT DET8 board x CU xx DET8 1580 8 zones expansion board Fault on the 1580 board FAULT Earth fault plus CU xx FAULT Earth fault minus CU xx Earth fault is detected Check all cables for damage etc The f...

Page 42: ...xx DET8 1580 8 zones expansion board Check for blown fuse on the 1580 board FAULT fuse for board 1582 no x CU xx 1582 External FBP interface board Check for blown fuses on the 1582 board FAULT Fuse o...

Page 43: ...on board No communication connection with the TLON network FAULT Low batt cap control unit xx Also indicated by LED Fault Power supply Battery voltage 21 9 V load resistor connected The battery is pre...

Page 44: ...ak gives the fault message FAULT Cut off When short circuit isolator 2370 is used Check the loop and the units connected on the isolated loop segment FAULT Output x techn no xxxxxx If the output is pr...

Page 45: ...ULT ROM memory control unit xx A fault in control unit xx SW This is very serious Call for service personnel engineer immediately FAULT RS232 comm in gateway CU xx Gateway GW512 is are installed in th...

Page 46: ...line on the 1580 board The wires cable may have been damaged NOTE As long as there is a short circuit the zone is disabled Each 10 minutes an attempt is made to re enable the zone again FAULT Site sp...

Page 47: ...n on the system loop between GW512 and the EBL1000 2000 Main Control Unit due to cable connection fault no not correct programming of the GW512 Sub Control Unit in the EBL1000 2000 system xx EBL512 co...

Page 48: ...BS4 Board x CU xx BS4 1584 Autronica interface board Cut off break on the BS4 loop This is indicating a single break on the loop Communication has to be performed in both directions to find all units...

Page 49: ...se or keys to scroll If a fault has been corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged When a fault is corrected and acknowledged...

Page 50: ...apter Programming SSD download page 50 17 2 Control Units in a TLON network In a TLON network there are two or more control units connected A TLON connection board 1590 is required in each control uni...

Page 51: ...V1 44 x 49 specific data SSD can be downloaded see chapter Programming SSD download page 50 17 2 1 TLON network programming configuration A PC is connected to the modular connector J2 in the control...

Page 52: ...2 After the downloading in the selected control unit an automatic reset restart will take place in that control unit see chapter Reset Restart page 55 If you select two or more control units the PC ha...

Page 53: ...lp 18 3 1 Download in Control unit The user definable text messages which are to be displayed in the control unit s ext FBP s alphanumeric display could be downloaded in one control unit for the whole...

Page 54: ...r JP4 RESET momentarily in position approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 Start the downloading...

Page 55: ...l unit is in Bootstrap mode 5 The Win512 settings dialog box shows default settings in the different fields Click the Read button to see the actual settings Then write the new settings in the fields r...

Page 56: ...ions EBL512 V1 44 x 54 20 1 Control Units in a TLON network All control units connected to a TLON network should have the same convention The number of addresses could vary and the language if require...

Page 57: ...SD via a PC Win512 FFD SSD SSI SW SSW Safe shut down Safe shut down of control unit menu H8 S5 will save the SSW data in a Flash ROM which saves the data although the control unit has no power supply...

Page 58: ...can be activated A fault is generated in the system and the following message will be shown in the display Regarding code xx and yy y see page 43 This fault is also indicated by LEDs Fault tx L19 and...

Page 59: ...menus have sub menus Use and to scroll between the sub menus e g B1 B9 Use A to accept If instead of a menu identification e g B1 the letter L is shown it means that it is a List Use and to scroll in...

Page 60: ...output s for routing equipment fire brigade tx may be disabled if programmed so in Win512 There will be an automatic test mode exit one hour after the latest tested alarm point See also chapter Perfo...

Page 61: ...nter if available will print out every tested alarm point Zone xxx Address xx Time HH MM Push A to stop the test mode Some regulations say that the fire alarm routing equipment Fire alarm tx also shou...

Page 62: ...s can not be disabled Up to 100 alarm points zones and or outputs can be disabled It is not possible to exceed the limit A warning message will be shown Don t forget to re enable via menus H2 B4 B6 or...

Page 63: ...rding to chapter Access see page 57 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 A Disable zone 000 ACCEPT Write zone number e g 001 Disable zone 001 ACCEPT Push A to acce...

Page 64: ...enu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B2 Disable zone address ACCEPT B2 A Disable zone 000 Address 00 ACCEPT Write zone number and address e g 001 01 Disable zo...

Page 65: ...0 RU SU 1 S 2 R 3 RE 4 ES ACCEPT 4 ES not shown in Swedish RUS convention Write C U No and push 0 RU4 2265 or SU4 2262 2263 1 S0 S3 2 R0 R1 or 3 Relay board 1581 4 1583 board output Extinguishing sys...

Page 66: ...her disablements in the system Action Text in display Comments Access According to chapter Access see page 57 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B...

Page 67: ...blements in the system Action Text in display Comments Access According to chapter Access see page 57 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B5 Re ena...

Page 68: ...ish RUS convention Push 0 RU4 2265 or SU4 2262 2263 1 S0 S3 2 R0 R1 or 3 Relay board 1581 4 1583 board output Extinguishing system Push A to accept A Depending on the chosen type 0 1 2 3 resp 4 the fo...

Page 69: ...e re enabled before the can generate a new fire alarm Action Text in display Comments Access According to chapter Access see page 57 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACC...

Page 70: ...ivated Control off is indicated by LED Disabled and is shown in menu H4 U1 Don t forget to re enable the outputs again i e Control on via menu H2 B8 50 Also the Extinguish equipment output on the Germ...

Page 71: ...U1 Don t forget to re enable the outputs again i e Alarm device on via menu H2 B9 NOTE This function is not the same as for push button Silence See chapter Push button Silence page 22 This function h...

Page 72: ...ant to see the SW version push Return instead of A to return to menu H3 because then there will be no changes of the time Action Text in display Comments Access According to chapter Access see page 57...

Page 73: ...ess According to chapter Access see page 57 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Push 1 for an automatic print out of all disablemen...

Page 74: ...r ACCEPT H4 A Disablement Printout 1 yes U1 Scroll to menu U2 Disablement by time channel Printout 1 yes U2 Push 1 for an automatic print out of all disablements in the system Push A for presentation...

Page 75: ...r Access see page 57 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Scroll to menu U3 Show open doors Printout 1 yes U3 Push 1 for an automati...

Page 76: ...ch other are in alarm status fire alarm will be activated in the system 52 When two or more units zone addresses dependent on each other are in alarm status fire alarm will be activated in the system...

Page 77: ...horised service personnel only must do the reset to default value Used incorrectly it can cause nuisance fire alarms 53 The first sensor week average value is calculated 10 minutes after SSD download...

Page 78: ...y values Printout 1 yes U6 Push A for display presentation or Push 1 for print out Alternative A Start Sensor 000000 Write the sensor s techn number and push A to accept E g 000001 A Sensor 000001 Val...

Page 79: ...sor has to be cleaned replaced soon See chapter Acknowledge SERVICE signal H8 S4 page 99 It is not possible to get a print out Action Text in display Comments Access According to chapter Access see pa...

Page 80: ...status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Scroll to menu U8 Show event log Printout 1 yes U8 Push A for display presentation or Push 1 for print out Alternative A When A...

Page 81: ...the texts presented in the display on the print outs It is not possible to get a print out Action Text in display Comments Access According to chapter Access see page 57 Scroll to menu H4 Present syst...

Page 82: ...ite specific data download of SW settings configurations C U system data create and download the user definable text messages shown in the alphanumeric display in the C U ext FBP and in the Display un...

Page 83: ...here Action Text in display Comments Access According to chapter Access page 57 Perform monthly test ACCEPT H1 Scroll to menu H5 Programming ACCEPT H5 A Access code _ If login was made with code for l...

Page 84: ...s to be performed to ensure the function When all alarm devices sounders etc have been connected including required resistors and when the SSD download is ready calibration has to be done as follows A...

Page 85: ...lt will be reduced NOTE Don t forget to turn off this mode after the commissioning Action Text in display Comments Access According to chapter Access code for programming H5 see page 81 Scroll to menu...

Page 86: ...n display Comments Access According to chapter Access code for programming H5 see page 81 Scroll to menu A3 Direction for communication on COM BS4 loop ACCEPT A3 A Select type of loop 0 0 COM 1 BS4 AC...

Page 87: ...nts Access According to chapter Access code for programming H5 see page 81 Scroll to menu A4 Show information about site specific data ACCEPT A4 A Name xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx 57 Downloaded...

Page 88: ...sented as 3800 mA Charging current 100 mA can not be correctly presented Action Text in display Comments Access According to chapter Access code for programming H5 see page 81 Scroll to menu A5 Displa...

Page 89: ...6 Display current consumption on COM BS4 loop ACCEPT A6 A Select type of loop 0 0 COM 1 BS4 ACCEPT Select type of loop Push A to accept Display current consumption on COM loop 0 unit 00 A or 1 A Displ...

Page 90: ...elation to pollings Answer are received answer faults or no answers number and faults in relation to pollings Action Text in display Comments Access According to chapter Access code for programming H5...

Page 91: ...ed Autronica interface board 1584 BY3 right pin 0 V BS4 board Autronica interface board 1584 Action Text in display Comments Access According to chapter Access code for programming H5 see page 81 Scro...

Page 92: ...hould be changed NOTE This code require eight 8 digits Action Text in display Comments Access According to chapter Access code for programming H5 see page 81 Scroll to menu A9 Change access code for P...

Page 93: ...de for programming H5 see page 81 Scroll to menu A10 Change access code for programming ACCEPT A10 A Access code _ New code Verify Enter the old code the new code and the new code again Access code Ne...

Page 94: ...8 page 78 When all faults are the LED Fault tx will be turned off Corresponding outputs will be reset When all faults are acknowledged and corrected serviced LED Fault will be turned off Corresponding...

Page 95: ...alarm point Perform the test as quickly as possible since the output for routing equipment fire brigade tx is disabled also the parts of the zones in test mode not visible for the test personnel are...

Page 96: ...l unit door is left open the output s for routing equipment fire brigade tx may be disabled if programmed so in Win512 A sensor in test mode will not be able to activate fault Action Text in display C...

Page 97: ...3 is required here Action Text in display Comments Access According to chapter Access see page 57 Scroll to menu H8 Maintenance ACCEPT H8 A Access code _ When required see above enter the access code...

Page 98: ...hen only local alarm is required Disabled outputs are indicated by LEDs Disabled L10 and Disabled Fire brigade tx L18 and or Disabled Fault tx L19 Action Text in display Comments Access According to c...

Page 99: ...apter Access code for maintenance see page 95 Scroll to menu S2 Disconnect COM Loop ACCEPT S2 A Disconnect type 0 0 COM 1 BS4 2 DET8 3 loop Unit ACCEPT Push 0 COM loop 1 BS4 loop 2 Expansion board 158...

Page 100: ...ct type 0 0 COM 1 BS4 2 DET8 3 Loop Unit ACCEPT Push 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 Push A to accept Re connect COM Loop 0 CU 00 ACCEPT Re connect BS4 Loo...

Page 101: ...ccording to chapter Access code for maintenance see page 95 Scroll to menu S4 Acknowledge SERVICE signal ACCEPT S4 A Sensor xxxxxx needs service L If there are no sensors to acknowledge menu S4 will b...

Page 102: ...play Comments Access According to chapter Access code for maintenance see page 95 Scroll to menu S5 Safe shut down of control unit ACCEPT S5 A Shut down control unit 00 0 1 Yes 0 No ACCEPT Write the C...

Page 103: ...ter Access code for maintenance see page 95 Scroll to menu S6 Activate address in alarm mode ACCEPT S6 A Select zone 000 address 00 ACCEPT Write the zone and address Select zone 123 address 45 ACCEPT...

Page 104: ...y key to return Push Return at once Return Shall control units be synchronized 0 1 Yes 0 No ACCEPT Before a new syncro nization wait until the syncronization is ready 61 Push Return to menu S7 Return...

Page 105: ...de for maintenance see page 95 Scroll to menu S8 Change access code for maintenance ACCEPT S8 A Access code _ New code Verify Enter the old code the new code and the new code again Access code New cod...

Page 106: ...ing to chapter Access see page 57 Scroll to menu H9 Change access code for daily duties ACCEPT H9 A Access code _ New code Verify Enter the old code the new code and the new code again Access code New...

Page 107: ...NOTE xx is depending on control unit Put back the fuse and acknowledge the fault Menu H6 Remove fuse F5 not F1 F4 on the connection board 1555 The following fault message is to be shown FAULT monitor...

Page 108: ...door Remove the old paper roll carefully cut the paper so that the paper within the printer remains there Take the new paper roll tape the new paper to the old paper and place the paper roll on the pr...

Page 109: ...the batteries and a fault will be activated if something goes wrong They are rechargeable sealed lead acid batteries and maintenance free but the producer s instructions are always to be followed The...

Page 110: ...tobacco smoking in connection with bad ventilation can cause a fire alarm Welding grinding cutting sawing drilling These kind of jobs cause smoke Carpet welding Welding of plastic carpets causes a smo...

Page 111: ...e could have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another type of detector can solve certain problems Bear also in mind that the coverage area can be...

Page 112: ...has been activated in the system contact your local dealer for cleaning replacement of the sensors detectors Metal objects must absolutely not be stuck into the sensor detector Static electricity may...

Page 113: ...Matsushita Electric Works Fire Security Technology AB MEW00442 Rev Operating Instructions EBL512 V1 44 x 111 37 Revision history Revision...

Page 114: ...This page has deliberately been left blank...

Page 115: ...This page has deliberately been left blank...

Page 116: ...Citadellsv gen 23 SE 211 18 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 Home page www mfstech com...