TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
25
of
26
•
NAC turns ON till system silence or reset action is carried out by user OR till silence time is not completed.
•
The fixed TWO Fire output of the relay gets activated.
•
Fire alarms latched and are not allowed to clear automatically.
•
Timer for NAC Silence starts.
•
If any zone is in Walk test mode, it exits the Walk test mode.
•
FIRE notification send to the FIRE CLOUD app
4.2.2 Fault Condition
If system detects any fault, it immediately enters into fault condition. The system indicates fault visually and
audibly with distinctive indication than fire alarm(0.5Sec ON/OFF). NAC is not active, the fixed fault output relay
(PFC relay) is activated. The system is able to recognise faults in Zone circuit, NAC circuit, Mains fail, Battery
Low/cut, etc. The system faults are shown on LCD as shown below.
For example,
Fault
→
Zone2: Short
Fault
→
NAC : Open
NAC Open
FAULT [1/1]
The System operation for the fault condition is given below.
•
LCD shows fault message
•
Respective zone fault LED turns ON.
•
Fixed Fault output of the relay (PFC Relay) gets activated.
•
NACs are not active.
•
Internal buzzer toggles 1 second ON and
5 seconds OFF till all faults are recovered.
•
Fault notification send to the FIRE CLOUD app
4.3
Factory Default
This function is specially use for default panel setting in factory default setting. If user want to delete all setting
please follow below step,
Zone 1 Short
FAULT [1/1]