TS 21 I-HC User Manual
Vighnaharta Technologies Pvt. Ltd
Page
13
of
19
Function names in the menu
Process Steps
4.
o1ZC
(Output 1 Zero calibration)
This is a calibration function used
to calibrate current output for
4mA.
o1SC
(Output 1 Span calibration) This
is a calibration function used to
calibrate current output for
20mA.
1.
Go to menu
o1ZC
.
2.
Measure current between
C+
and
C-
connections on
CON2
.
3.
Press
Up
or
Down
key to increase or decrease the
count to get
4mA
output across C+ and C-.
4.
Press
ENTER
key to save the count.
5.
Go to menu
o1SC
.
6.
Measure current between
C+
and
C-
connections on
CON2
.
7.
Press
Up
or
Down
key to increase or decrease the
count to get
20mA
output across C+ and C-.
8.
Press
ENTER
key to save the count.
9.
Press
ESCAPE
key to exit from Configuration mode
and remain in Idle or Scan mode.
5.
o2ZC
(Output 2 Zero calibration)
This is a calibration function used
to calibrate voltage output for
0V.
o2SC
(Output 2 Span calibration) This
is a calibration function used to
calibrate voltage output for 5 /
10V depending on voltage range
set in menu
A oP
.
1.
Go to menu
A oP
.
2.
Press
Up
or
Down
key to select 0 – 5v or 0 -10v
range.
3.
Go to menu
o2ZC
.
4.
Measure voltage between A-O/P and GND
connections on CON2.
5.
Press
Up
or
Down
key to increase or decrease the
count to get 0V output across A-O/P and GND.
6.
Press
ENTER
key to save the count.
7.
Go to menu
o2SC
.
8.
Measure voltage between A-O/P and GND
connections on CON2.
9.
Press
Up
or
Down
key to increase or decrease the
count to get 5v or 10v output across A-O/P and
GND.
10.
Press
ENTER
key to save the count.
11.
Press
ESCAPE
key to exit from Configuration mode
and remain in Idle or Scan mode.
6.
bAUd
This menu displays current baud rate depending on the
DIP switch positions. This value gets updated only
when unit is reset. This is a read only menu.
7.
PArt
This menu displays current parity set for modbus
communication using DIP switches. This value gets
updated only on reset. This is a read only menu.
8.
Addr
This menu displays current slave address set for
modbus communication using DIP switches. This value
gets updated only on reset. This is a read only menu.