15
Separating the neutralising system (if installed) from the boiler
and connecting the drain hose
C
B
A
1.
Separate hose
A
to the neutralising
system from siphon
B
.
2.
Connect drain hose
C
to the con-
densate drain of the siphon and run
to a drainage system.
Checking the neutralising system (if installed)
1.
Check the pH value of the conden-
sate downstream of the neutralising
system with a pH test strip. Replace
the granulate if the pH value is
< 6.5.
Note
Part no. for pH test strips: 9517 678.
Observe the neutralising system
manufacturer's instructions.
2.
Reinstall neutralising system in
reverse order.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)