5
Fig. 7
Remove blank screw using Allen key.
Fig. 8
Install burner support bracket (10mm hex extension bolt).
NG burner to Vitoflame 200
(continued)
5352 565 v1.0
Installation
18. Remove blank screw from front
burner plate and replace it with
support bracket - extension bolt
(Fig. 7 and 8).
19. Fire the burner and make final
burner adjustment using a
combustion analyzer.
20. For Natural gas the CO
2
level
should be around
9.4%, Oxygen O
2
- 4.1% and
CO<25 ppm.
21. Log the final setting results and
attach printout from the
analyzer to test sheet on the
last page.
22. Fax the test results to
(519) 885-1134 immediately
after the installation.