19
Fault
Red flash
code
Cause of fault
Action
Burner starts and flame
builds, but burner enters
fault state after safety time
expires
2
×
Flame monitor contaminated
Clean flame monitor
2
×
Flame monitor receives insuffi-
cient light
Clean sensor plate
2
×
Flame monitor faulty
Replace flame monitor
2
×
Burner control unit faulty
Replace burner control unit
2
×
Carbon deposits on the flame
tube or on the sensor plate
Clean the flame tube and sensor
plate
Flame tears off more than
3 times during operation
7
×
Air in suction line
Seal line and filter
7
×
Nozzle faulty
Replace nozzle
7
×
Burner incorrectly adjusted
Set default values (see chapter
"Standard values for burner ad-
justment")
7
×
Sensor plate contaminated
Clean sensor plate
Ignition switches on during
operation
7 x
Flame monitor contaminated
Clean flame monitor
7 x
Sensor plate contaminated
Clean sensor plate
7 x
Nozzle contaminated or faulty
Replace nozzle
Condensate backup in flue
gas heat exchanger
7 x
Siphon or neutralising system
contaminated
Clean siphon and neutralising
system
Faults without flash code indication
Fault
Cause of fault
Action
Burner does not start (no
fault display), indicator
does not illuminate
No power
Check fuse or plug-in connector
aBÖ
in
the control unit, the electrical connec-
tions, the setting of the ON/OFF switch
on the control unit and the mains isolator
High limit safety cut-out has responded
Press reset button at the boiler control
unit
The low water indicator has caused the
system to shut down
Check the water level; top-up if required.
Press the reset button on the burner.
Servomotor faulty
Replace the servomotor
When changing from stage
1 to stage 2, the flame
tears off and the burner
starts again
Flame monitor contaminated
Clean flame monitor
Inside of flame tube contaminated
Clean inside of flame tube
Sensor plate contaminated
Clean sensor plate
Faulty control unit
Replace control unit
Solenoid valve stage 2 faulty
Replace solenoid coil
Burner sooty
Insufficient or excess air
Correct the settings. Check and clean im-
peller.
Check fan pressure.
Check ventilation in installation room.
Insufficient chimney draught
Check chimney and flue gas routing
Nozzle faulty
Replace the nozzle, fit the right nozzle
(see chapter "Standard values for burner
adjustment")
The flame tube extension is missing
Install the flame tube extension
CO
2
content too low
Incorrect setting
Check setting (see chapter "Standard val-
ues for burner adjustment")
Troubleshooting
Diagnosis
(cont.)
5831447