Parameters are split into the following groups:
–
"General"
–
"Boiler"
–
"DHW"
(domestic hot water)
–
"Heating circuit 1/2/3"
–
"Solar"
■
Heating systems with one heating circuit without
mixer and one or 2 heating circuits with mixer:
Below, the heating circuit without mixer is designated
"Heating circuit 1"
and the heating circuits with
mixer as
"Heating circuit 2"
or
"Heating circuit 3"
.
If the heating circuits have been renamed, the
chosen designation appears.
Note
The display and setting of some parameters is
dependent on:
■
Heat generator
■
Connected accessories and the functions associated
with them
Tap the following buttons:
1.
and
OK
– press simultaneously for approx. 4 s,
then release.
2.
Use
/
to select
"System configuration"
.
3. OK
4.
Use
/
to select the required group.
5. OK
6.
Use
/
to select the parameter to be set. See
tables below.
7. OK
8.
/
for the required value.
9. OK
General
Note
Parameter values in
bold
are factory settings.
508.0 "UTC time zone"
Setting
Explanations
Setting of the UTC time zone in which the appliance is
located.
2
The factory setting is UTC +1 h
–
24 to +24 Time difference adjustable from
–
12 h to +12 h in in-
crements of 0.5 h
528.0 "Set flow temperature for external demand"
Setting
Explanations
Set flow temperature for external demand
70
Set flow temperature in the delivered condition 70 °C
20 to 82
Set flow temperature adjustable from 20 to 82 °C in
1 °C increments
896.0 "Display correction for outside temperature"
Setting
Explanations
Correction of measured outside temperature
0
Correction in the delivered condition 0 K
-10 to + 10 Correction adjustable from -10 to + 10 K in 1 K incre-
ments
System configuration (parameters)
Calling up parameters