88
Coding in the delivered condition
Possible change
90:128
Time constant for calcu-
lating adjusted outside
temperature 21.3 h
90:1
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature, sub-
ject to the set value when
the outside temperature
changes
1 step
≙
10 min
94:0
Without OpenTherm ex-
tension
94:1
With OpenTherm exten-
sion (automatic recogni-
tion)
95:0
Without Vitocom 100,
type GSM communica-
tion interface
95:1
With Vitocom 100,
type GSM communication
interface (automatic recog-
nition)
97:0
With LON communication
module: the outside tem-
perature of the sensor
connected to the control
unit is utilised internally
(only for weather-com-
pensated control units)
97:1
Control unit receives out-
side temperature
97:2
The control unit transmits
the outside temperature to
the Vitotronic 200-H
98:1
Viessmann system num-
ber
In conjunction with moni-
toring several systems
via Vitocom 300
98:1
to
98:5
System number adjustable
from 1 to 5
99:0
Never adjust
9A:0
Never adjust
9b:70
Set flow temperature for
external demand 70 °C
9b:0
to
9b:127
Set flow temperature for
external demand adjusta-
ble from 0 to 127 °C (limited
by boiler-specific parame-
ters)
9C:20
Monitoring LON subscrib-
ers
9C:0
No monitoring
9C:5
to
Time adjustable from 5 to
60 min
Code 2
General/group "1"
(cont.)
5585 174 GB