Vitodens 200-W, B2HA 19 to 80 Technical Data
5683 717 - 03
16
Note:
for multiple boiler applications when using the Vitodens 200-W, B2HA boilers, refer to the multiple boiler
low-loss distribution manifold installation instructions.
*1 For system
t
< 20° F use low-loss header sizes for
t
20° F.
*2 Low-Loss temperature sensor - standard equipment of the cascade control Vitotronic 300-K MW2B:
for use in multiple boiler applications.
Boiler
Model
No. of
Boilers
Boiler
Max.
Flow
Rate
Total
Flow
Rate
Typical System Flow Rates
Viessmann
Low-loss
Temp.
Sensor
Required*2
t
*1
°F
(°C)
20
(11.0)
25
(14.0)
30
(17.0)
35
(19.5)
40
(22.0)
B2HA
60
2
15.4
(3500)
30.8
(7000)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
38.8
(8813)
Yes
160/80
31
(4050)
Yes
120/80
26
(5875)
Yes
120/80
22.2
(5036)
Yes
120/80
19.4
(4406)
Yes
80/60
Yes
B2HA
60
3
15.4
(3500)
46.2
(10500)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
58.2
(13220)
Yes
200/120
46.6
(10576)
Yes
200/120
38.8
(8813)
Yes
160/80
33.3
(7554)
Yes
120/80
29
(6610)
Yes
120/80
Yes
B2HA
60
4
15.4
(3500)
61.6
(14000)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
77.6
(17626)
Yes
200/120
62
(14101)
Yes
200/120
51.7
(11750)
Yes
200/120
44.3
(10072)
Yes
200/120
38.8
(8813)
Yes
160/80
Yes
B2HA
60
5
15.4
(3500)
77
(17500)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
97
(22031)
Yes
250/150
77.6
(17625)
Yes
200/120
64.7
(14687)
Yes
200/120
55.4
(12589)
Yes
200/120
48.5
(11015)
Yes
200/120
Yes
B2HA
60
6
15.4
(3500)
92.4
(21000)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
116.4
(26439)
Yes
250/150
93.1
(21151)
Yes
250/150
77.6
(17626)
Yes
200/120
66.5
(15108)
Yes
200/120
58.2
(13220)
Yes
200/120
Yes
B2HA
60
7
15.4
(3500)
107.8
(24500)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
135.8
(30846)
Yes
300/200
108.6
(24677)
Yes
250/150
90.5
(20564)
Yes
250/150
77.6
(17626)
Yes
200/120
68
(15423)
Yes
200/120
Yes
B2HA
60
8
15.4
(3500)
123.2
(28000)
System Flow
Rate
LLH Required
LLH Model
GPM
(L/h)
155.2
(35252)
Yes
300/200
124.2
(28202)
Yes
300/200
103.5
(23502)
Yes
250/150
88.7
(20144)
Yes
250/150
77.6
(17626)
Yes
200/120
Yes
Sizing of Low-Loss Header in a Commercial Multiple-Boiler Application
Low-Loss Header Information
Low-Loss Header Application
(continued)