Vitodens 200-W, B2HA 19 to 80 Technical Data
11
5683 717 - 03
System Flow Rates
11
Typical System Flow Rates
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HA 19
1 boiler
Output (NG/LPG)
MBH
61
t for NG/LPG
20º F rise GPM (L/h) 6.1
(1385)
25º F rise GPM (L/h)
4.9 (1113)
30º F rise GPM (L/h)
4.0 (909)
35º F rise GPM (L/h)
3.5 (795)
40º F rise GPM (L/h)
3.1 (704)
Model B2HA 28
1 boiler
Output (NG/LPG)
MBH
91.2
t for NG/LPG
20º F rise GPM (L/h) 9.1
(2100)
25º F rise GPM (L/h)
7.3 (1700)
30º F rise GPM (L/h)
6.1 (1400)
35º F rise GPM (L/h)
5.2 (1200)
40º F rise GPM (L/h)
4.6 (1000)
Model B2HA 35
1 boiler
Output (NG/LPG)
MBH
114
t for NG/LPG
20º F rise GPM (L/h) 11.4
(2589)
25º F rise GPM (L/h)
9.1 (2067)
30º F rise GPM (L/h)
7.6 (1726)
35º F rise GPM (L/h)
6.5 (1476)
40º F rise GPM (L/h)
5.7 (1295)