65
5608 741 - 04
Vitodens Rigid and Flex Venting Systems Installation
Side Wall Vent Termination
For PP(s) systems, all exhaust vent and air intake piping
and elbows exposed outside, must be UV resistant
polypropylene (supplied by the vent manufacturer).
Installation of field supplied vent riser
Side wall vent termination (side view)
Side wall vent termination (front view)
IMPORTANT
All PP(s) vent termination elbows, must be secured in
place as specified by the manufacturer.
IMPORTANT
Grade or Max.
snow level
Support bracket
Attach termination
elbow with screen
Side wall
Caulk
min. 12 in.
(305 mm)
max. 36 in.
(914 mm)
Vent
riser
Exhaust vent terminal,
45° or 90°
Grade or Snow Level
min 12 in. (305 mm)
max 9 in.
(229 mm)
All PP(s) vent termination
elbows must be secured in
place as specified by the
vent manufacturer.
min. 6 in.
(152 mm)
Flue
Single Pipe Venting (Room Air Dependent)