63
Vitocrossal boiler
Rated heating output
P
n
: TF/TR = 80/60
kW
121 to 727
152 to 909
P
cond
: TF/TR = 50/30
kW
133 to 800
167 to 1000
Rated heat input
*2
kW
127 to 762
159 to 953
Boiler product ID
CE-0085CS0411
Permiss. operating temperature
°C
95
95
Permiss. flow temperature
(= safety temperature)
°C
110
110
Max. permiss. operating pressure
bar
6
6
MPa
0.6
0.6
Min. permiss. operating pressure
bar
0.5
0.5
MPa
0.05
0.05
Test pressure
bar
7.8
7.8
MPa
0.78
0.78
Boiler body dimensions
Length
mm
2241
2441
Width
mm
960
960
Height
mm
1676
1676
Overall dimensions
Length
mm
3187
3389
Width
mm
1060
1060
Height
mm
1676
1676
Foundation dimensions
Length
mm
2500
2700
Height
mm
1200
1200
Weight
Handling weight (boiler body)
kg
1150
1200
Transport weight (burner)
kg
120
120
Total weight, dry
kg
1435
1492
Total weight, filled
kg
2585
2672
Water capacity
l
1150
1180
Connections
Boiler flow
PN 6 DN
100
100
Boiler return
PN 6 DN
100
100
2nd boiler return
PN 6 DN
100
100
Flue gas parameters
*3
Flue gas temperature (50/30 °C)
■
At rated heating output
°C
43
45
■
At partial load
°C
34
35
Flue gas temperature (80/60 °C)
■
At rated heating output
°C
67
69
■
At partial load
°C
63
63
*2
Sizing up to NHN 1500 m
*3
Values for calculating the size of the flue system to EN 13384, based on 10 % CO
2
for natural gas
Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
The details for partial load refer to the lower rated heating output. If the partial load differs (subject to burner operating
mode), calculate the flue gas mass flow rate accordingly.
Specification
Specification
5816717
Содержание VITOCROSSAL CRU 1000 kW
Страница 23: ...23 6x 2 3 1 Fig 13 Commissioning inspection maintenance Opening the burner door 5816717 ...
Страница 44: ...44 Troubleshooting Faults without fault display cont 5816717 Diagnosis ...
Страница 69: ...69 5816717 ...
Страница 70: ...70 5816717 ...
Страница 71: ...71 5816717 ...