13
A
B
Fig. 4
1.
Turn adjusting screw
A
on the main volume but-
terfly of the gas train fully towards "
–
." Turn back 4
turns towards "
+
".
2.
Insert the coding card for P gas into the burner
control unit. See the following chapter.
Note
Coding card must be ordered separately.
3.
Adjust gas pressure switch
B
to a new value:
■
To 40 mbar for a nominal supply pressure (flow
pressure) of 50 mbar
■
To 25 mbar for a nominal supply pressure (flow
pressure) of 37 mbar
4.
Start the burner.
5.
Measure the CO
2
content in the flue gas and
adjust. See page 16.
Commissioning, inspection, maintenance
Conversion to LPG P
5816717