Plume management kit
The plume kit enables the relocation of the flue outlet of a standard horizontal flue
system to another position and is available as an optional extra.
Ensure the maximum length of 3 m
(externally) and 7 m (internally) is
not exceeded
The maximum length is reduced by 1 m
when using a further 87° bend or
2 x 45° bends
Deduct 3 m from the maximum possible
standard concentric horizontal flue length
and add the standard plume kit maximum
length to give maximum length of entire
flue system. ie. 6 m - 3 m + 2 m = 5 m
maximum
Item
Part no.
A
Plume kit standard delivery 2 m max. length
7373238
B
Plume kit standard delivery additional options
2 x 87° bends
7373267
1 pipe 1 m long
7373268
C
Plume kit standard delivery additional option
2 x 45° bends
7373266
1 pipe 1 m long
7373268
Fixing clamps
7246572
The standard plume kit comprises of
the following parts:
87° connection to horizontal terminal
1 m pipe extension
87° flue outlet elbow with bird mesh
Fixing clamps
B
C
A
Typical routing options
Installed to prevent nuisance
pluming across the window
Kit contents
28/29