11
!
Please note
To prevent material damage, site the buffer cyl-
inder in a draught-free room free from the risk of
frost.
When not in use, the buffer cylinder must be
drained if there is a risk of frost.
■
Provide adequate clearance from the wall to allow for
operation of the temperature controller (if installed).
■
Placing the heating water buffer cylinder on a plinth
will make the room easier to clean.
■
Use the adjustable feet to level the buffer cylinder.
Note
Only use one or two of the adjustable feet to level the
cylinder body. At least one of the adjustable feet must
remain fully screwed in.
≤
35
Fig. 5
Do
not
extend the adjustable feet beyond a total
length of 35 mm.
Vitocell with immersion heater, type SVW
a
Fig. 6
Immersion heater installation instructions
Maintain the minimum clearance.
Note
The unheated length of any threaded immersion
heater installed on site must be at least 100 mm.
Vitocell
Capacity
Dim. a
Output of immersion heater
Type SVW
200 l
min. 650 mm
6 kW
Vitocell 100-E/100-W, type SVW
!
Please note
The thermal insulation must not come into con-
tact with naked flames.
Exercise caution when welding and brazing.
1.
Install the cylinder temperature sensors; see
page 23.
Installation sequence
Siting the Vitocell
6154032
Installation