13
Cables/leads
E
L
A
F
K
D
C
B
M
H
G
Q
P
N
R
Fig. 5
A
Heat pump
B
LV lead, pre-manufactured
C
Control cable, pre-manufactured
D
Flexible power cable (special tariff/load current):
According to compressor output, cable length and
routing, e.g. 5 x 2.5 mm
2
.
E
Outside temperature sensor, sensor lead:
2 x 0.75 mm
2
F
Control unit, flexible power cable: 5 x 1.5 mm
2
with
power-OFF contact power cable, floating
G
Electricity meter/mains
H
DHW cylinder
K
Cylinder temperature sensor, sensor lead:
2 x 0.75 mm
2
L
DHW circulation pump, power cable: 3 x 1.5 mm
2
M
Flexible power cable for instantaneous heating
water heater (accessories):
400 V: 5 x 2.5 mm
2
230 V: 7 x 2.5 mm
2
N
Heating water buffer cylinder
P
Secondary pump, power cable: 3 x 1.5 mm
2
Q
Heating circuit pump
R
Buffer temperature sensor, sensor lead:
2 x 0.75 mm
2
Required cable/lead lengths:
■
For the heat pump control unit (wall outlet centrally
directly below the heat pump control unit):
0.6 m from wall outlet
■
Inside the heat pump (to the control panel):
3.4 m plus wall clearance
External heat pump
Installation requirements
■
Provide a manual drain for the heating water flow
and return lines in any area at risk from frost.
If the heat pump control unit and heating circuit
pump are ready for operation, the frost protection
function of the heat pump control unit is enabled.
Drain the system if the heat pump is shut down or
there is a prolonged power failure.
On heat pump systems where a power failure cannot
be recognised (holiday home), operate the heating
circuit with a suitable antifreeze or drain it.
■
To prevent "air short circuits" and an increase in
noise level due to reflection, avoid siting equipment
in recesses, at building corners or between 2 walls.
Lawn areas and vegetation can reduce noise gener-
ation.
Therefore,
only
the heat pump foundations should
be made from reverberant material (concrete).
■
Never install the heat pump next to living rooms or
bedrooms.
■
The air in the discharge area is approx. 10 K colder
than the ambient air. Therefore, black ice could
develop in the discharge area even at [ambient] tem-
peratures above freezing. A clearance of
≥
3 m must
be observed to pavements or patios.
Note
During defrosting, cool vapour escapes from the heat
pump air discharge vents. This vapour build-up must
be taken into consideration during installation (choos-
ing the installation location, orientation of the heat
pump).
Preparing for installation
Internal heat pump
(cont.)
5692878
Installation
Содержание Vitocal 350-A AWHI 351.A14
Страница 22: ...22 Fig 13 Installation sequence Type AWHI 351 A only Fitting the supplied floor mat 5692878 Installation ...
Страница 26: ...26 3x 8 9 3x 3x 3x Fig 17 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 27: ...27 10 3x 3x 2x 11 Fig 18 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 30: ...30 Type AWHI 351 A 1 Fig 22 Installation sequence Siting the heat pump cont 5692878 Installation ...
Страница 66: ...66 Fitting the front panel 1 2 Fig 64 Installation sequence Closing the heat pump cont 5692878 Installation ...
Страница 82: ...82 Troubleshooting Repairs cont 5692878 Maintenance ...
Страница 101: ...101 Parts list type AWHI 351 A Heat pump module cont 5692878 Components ...
Страница 104: ...104 Parts list type AWHI 351 A Base frame cont 5692878 Components ...
Страница 110: ...110 Silencer hood 0001 0002 0001 Fig 86 Parts list type AWHO 351 A Casing cont 5692878 Components ...
Страница 114: ...114 0007 0007 0003 0005 0003 0002 0001 0006 0005 0008 Fig 88 Parts list type AWHO 351 A Air module 5692878 Components ...
Страница 125: ...125 Parts list type AWHO 351 A Heat pump module cont 5692878 Components ...