15
Types 221.A10 to A16, 230 V~ and 400 V~
B
A
1000
a
A
B
a
100
300
1000
200
Fig. 5
A
Air intake
B
Air discharge
a
■
Line entry above ground level:
≥
200 mm
■
Line entry below ground level:
≥
900 mm
Transport and siting
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never
apply loads/weight to the top, front or
side panels of the appliance.
!
Please note
If the compressor in the outdoor unit is strongly
tilted, lubricant will enter the refrigerant circuit
and damage the appliance.
Max. tilting angle: 45° for approx. 4 min, other-
wise 30°
Floorstanding installation
Foundations
Fit the floor supports on 2 horizontal foundation strips.
We recommend the construction of concrete founda-
tions in accordance with the following diagram. The
stated thickness of the layers represents an average
value. These values should be adjusted to suit the
local conditions. Follow the standard rules of building
engineering.
Installation sequence
Installing the outdoor unit
(cont.)
5831412
Installation
Содержание Vitocal 222-A
Страница 80: ...80 Fig 64 Maintenance Indoor unit Placing the control unit panel in its service position 5831412 Maintenance...
Страница 92: ...92 Maintenance Checking the fuses cont 5831412 Maintenance...
Страница 102: ...102 0004 0005 0001 0002 0003 0006 0007 Fig 74 Indoor unit parts lists Miscellaneous 5831412 Components...
Страница 104: ...104 Indoor unit parts lists Miscellaneous cont 5831412 Components...
Страница 112: ...112 Outdoor unit parts list 230 V types 221 A04 to A08 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 120: ...120 Outdoor unit parts list 230 V types 221 A10 to A16 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 154: ...154 5831412...
Страница 155: ...155 5831412...