Viessmann 5443202
|
8
SCU124
R2
S1
S2
R1
S3
S4 / TR
System layout 2
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Sensor S3 is used for a thermostatic function, which ope-
Arr 2
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
18
FLL
x*
ODB filling time active
-
18
STAB
x*
ODB stabilization in progress
-
18
COL
x
Temperature collector
S1
18
TSTB
x
Temperature tank 1 bottom
S2
18
TSTT
x
Temperature tank 1 at the top
S3
18
TDIS
s*
Thermal disinfection temperature
S3
18
S4
x
Temperature sensor 4
S4
18
TR
x*
Temperature return sensor
S4
18
n1 %
x
Pump speed R1
R1
19
h P1
x
Operating hours R1
R1
19
h P2
x
Operating hours R2
R2
19
kWh
x*
Heat quantity kWh
-
19
MWh
x*
Heat quantity MWh
-
19
CDIS
s*
Countdown of monitoring period
-
19
SDIS
s*
Starting time display
-
19
DDIS
s*
Heating period display
-
19
TIME
x
Time
-
16
rates relay 2 for backup heating or heat dump purposes,
when the adjusted thermostat switch-on temperature
(AH O) is reached. This function can optionally be com-
bined with up to three adjustable time frames.
Sensor S3 can also be optionally used as a reference sensor
for the thermal disinfection function OTD.
Sensor S4 can optionally be connected for measurement
purposes. If energy metering (OHQM) is activated, sensor
S4 has to be connected as return sensor.