background image

22

Check with the relevant supplier whether antifreeze
may affect system components that are not part of
the boiler, such as pumps, electrically and pneumati-
cally driven valves, other types of valves, gaskets,
etc.

If the system is filled with antifreeze, it must be
marked accordingly.

If a boiler system is changed to operate without anti-
freeze, flush the system in order to remove all traces
of the antifreeze.

The quality of the boiler water and feedwater must
meet the requirements of Directive VDI 2035.

The systems must be designed as sealed unvented
systems, as the antifreeze inhibitors decrease rapidly
if airborne oxygen is allowed to enter.

Diaphragm expansion vessels must comply with
DIN 4807 [or local regulations].

Solder connections should preferably be made with
Ag or Cu hard solder. If liquids containing chlorides
are used for soft soldering, any deposits must be
removed from the circuit afterwards through thor-
ough flushing. A higher chloride content in the heat
transfer medium can cause corrosion damage.

Only use oxygen diffusion-resistant hoses or metal
hoses for flexible connections.

Never equip the system on the primary side with
zinc-plated heat exchangers, containers or pipes as
zinc can be corroded by glycol/water mixtures.

To avoid the risk of corrosion, ensure that there is no
difference in electrical potential between system
components that are in contact with antifreeze.

Route all pipes in such a way that circulation cannot
be interrupted by gas cushions or deposits.

The water circuit must always be filled up to the high-
est point with the heat transfer medium.

After filling, ensure there are no more air cushions in
the system. When the temperature falls, gas cush-
ions form negative pressure and this can draw air
into the system.

After initial filling and commissioning, but after 14
days at the latest, clean the integral dirt trap so the
heat transfer medium can flow freely.

Following any losses through leaks or drawing off,
top up the antifreeze solution according to the con-
centration already in place. Establish the volume of
antifreeze as a check.

Water quality

Using antifreeze in boilers

 (cont.)

5692701

Appendix

Содержание PV1

Страница 1: ...Service instructions for contractors VIESMANN Vitoplex 100 Type PV1 150 to 620 kW Oil gas boiler VITOPLEX 100 5692701 GB 1 2018 Please keep safe ...

Страница 2: ...ocally applicable standards a ÖNORM EN ÖVGW G K directives ÖVGW TRF and ÖVE c SEV SUVA SVGW SVTI SWKI VKF and EKAS guideline 1942 LPG part 2 Safety instructions for working on the system Working on the system Where gas is used as the fuel close the main gas shut off valve and safeguard it against unintentional reopening Isolate the system from the power supply e g by removing the separate fuse or ...

Страница 3: ...c distribution board Danger If water escapes from the appliance there is a risk of scalding Never touch hot heating water Condensate Danger Contact with condensate can be harmful to health Never let condensate touch your skin or eyes and do not swallow it Flue systems and combustion air Ensure that flue systems are clear and cannot be sealed for instance due to accumulation of conden sate or other...

Страница 4: ...equirements 20 Prevention of damage due to scaling 20 Prevention of damage due to corrosion on the water side 21 Using antifreeze in boilers 21 5 Commissioning service reports Water quality 23 Maintenance service 23 6 Specification 25 7 Decommissioning and dis posal Final decommissioning and disposal 26 8 Certificates EU Declaration of Conformity 27 Manufacturer s certificate 28 9 Keyword index 29...

Страница 5: ...ot required during inspection Steps required during maintenance Not required during maintenance Intended use The appliance is only intended to be installed and operated in sealed unvented heating systems that comply with EN 12828 with due attention paid to the associated installation service and operating instruc tions as well as the details in the datasheet It is only designed for the heating up ...

Страница 6: ...0 12 Checking the expansion vessel and system pressure 10 13 Checking the temperature controller setting if a building management system is used DCC system 11 14 Checking electrical plug in connections and cable grommets for firm seating 15 Checking the thermal insulation 16 Checking the water quality 12 17 Cleaning the sight glass in the boiler door 12 18 Checking the mixer for ease of operation ...

Страница 7: ...ting the system from cold This also applies when restarting after main tenance and cleaning work Please note During boiler heat up unpleasant fumes and odours can result from outgassing from the thermal insulation the thermal block and the paint Ventilate the room during commissioning 12 Once the flow temperature has been reached successively switch on the heat consumers Switch the burner over to ...

Страница 8: ...s A without applying force 2 Clean flues B and combustion chamber C with the brush Remove combustion residues with a vacuum cleaner D Fig 3 3 Use a vacuum cleaner to remove combustion resi dues from the flue and the flue outlet through cleaning aperture D in the flue outlet Commissioning inspection maintenance Opening the boiler door and cleaning cover 5692701 ...

Страница 9: ... A Fig 4 1 Push turbulators A approx of their length into hot gas flues B 2 Bend turbulators approx 10 to 15 3 Push the turbulators into the hot gas flues as far as they will go When doing this check the pre stress ing Note Ensure that the turbulators cannot easily be pulled out of the hot gas flues Securing the boiler door and cleaning cover Note On gas burners mount the gas supply pipe Danger Es...

Страница 10: ...r side for tight ness Checking the function of the safety equipment Check the safety valves water level and pressure lim iter in accordance with manufacturer s instructions Checking the expansion vessel and system pressure Expansion vessel manufacturer s documentation Note Carry out this test on a cold system Commissioning inspection maintenance Securing the boiler door and cleaning cover cont 569...

Страница 11: ...er service life of the system components Boiler out put kW Up to 300 Up to 500 Up to 1000 Expansion vessel litres 50 80 140 Please note The ingress of oxygen can result in system dam age as a consequence of oxygen corrosion Only use pump controlled pressure maintaining systems that are sealed against corrosion The pressure maintaining systems must be protected against oxygen ingress into the heati...

Страница 12: ...t glass in the boiler door Fig 6 Check the gaskets and hose connection for leaks Checking the mixer for ease of operation and tightness 1 Remove the motorised lever from the mixer han dle 2 Check the mixer for ease of operation 3 Check the mixer for tightness Replace the O rings if the mixer leaks 4 Click the motorised lever into place Checking the function of the return temperature raising facili...

Страница 13: ...the low flue gas temperatures that may occur In the event of frequent cycling in standby mode and for partial loads below 40 we recommend the fol lowing Insulate the flue gas collector Install a motorised flue gas damper Set the minimum boiler runtime to 10 min This extends the service life and reduces running costs Instructing the system user The installer should instruct the user in the operatio...

Страница 14: ...14 Commissioning inspection maintenance Operating and service documents cont 5692701 ...

Страница 15: ...on number of the part from this parts list Pos Part not shown 300 Installation instructions 301 Service instructions 302 Thermal insulation small parts 303 Touch up spray paint Vitosilver 304 Touch up paint stick Vitosilver 305 Flame tube gasket Parts lists Ordering parts 5692701 Components ...

Страница 16: ...019 013 009 001 008 007 005 002 006 004 010 206 205 022 020 008 200 210 B 211 Fig 7 B Boiler control unit see parts list in the service instructions of the boiler control unit Parts lists Parts 5692701 Components ...

Страница 17: ...le 009 Gasket Ø 18 mm 010 Thermal insulation block 011 Thermal insulation mat 013 Gasket 20 x 15 mm 019 Cleaning brush Wearing part 020 Brush handle accessories 021 Extension piece accessories 022 Turbulator extractor accessories 200 Front panel top 205 Top panel right 206 Top panel left 210 Control unit fascia 211 Edge protection Parts lists Parts cont 5692701 Components ...

Страница 18: ...201 018 203 204 208 015 015 204 014 A 212 207 C C 209 Fig 8 A Type plate either right or left C Burner cable see parts list in the service instruc tions of the boiler control unit Parts lists Parts 5692701 Components ...

Страница 19: ... Side panel back left 204 Side panel front left and back right 207 Thermal insulation jacket 208 Thermal insulation mat back 209 Vitoplex 100 logo 212 Side panel front right with pos 209 Information on pos 014 Rated heating output kW 150 200 250 310 400 410 500 620 Quantity 20 22 26 26 30 30 40 45 Parts lists Parts cont 5692701 Components ...

Страница 20: ...up water Enter the volume of fill water and the water hardness into the boiler maintenance checklists For systems with a specific system volume 20 l kW heating output in multi boiler systems apply the out put of the smallest boiler follow the requirements for the next highest category of total heating output in accordance with the table In the case of serious deviations 50 l kW soften down to a to...

Страница 21: ...eless used This system separation must sepa rate the water flowing through the plastic pipes from other heating circuits e g from the heat generator by the provision of a corrosion resistant heat exchanger No further anti corrosion measures are required for sealed unvented hot water heating systems subject to the above points being observed However take addi tional precautions where there is a ris...

Страница 22: ...at transfer medium can cause corrosion damage Only use oxygen diffusion resistant hoses or metal hoses for flexible connections Never equip the system on the primary side with zinc plated heat exchangers containers or pipes as zinc can be corroded by glycol water mixtures To avoid the risk of corrosion ensure that there is no difference in electrical potential between system components that are in...

Страница 23: ...al hardness of the feed and top up water 0 11 dH total of alkaline earths 0 02 mol m3 pH value between 9 and 10 5 Maintenance service Commissioning Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Commissioning service reports Water quality 5692701 Appendix ...

Страница 24: ...vice Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Maintenance service Maintenance service Maintenance service Date By Commissioning service reports Maintenance service cont 5692701 Appendix ...

Страница 25: ...ated heating output C 215 At partial load 60 C 155 Product ID CE 0085BP0365 Standard seasonal effi ciency to DIN at Heating system temperature 75 60 C 86 Hs gross cv 2 Values for sizing the flue system to EN 13384 relative to 13 CO2 for fuel oil EL and 10 CO2 for natural gas Specification Specification 5692701 Appendix ...

Страница 26: ...ot part of ordi nary household waste For decommissioning the system isolate the system from the power supply and allow components to cool down where appropriate All components must be disposed of correctly Decommissioning and disposal Final decommissioning and disposal 5692701 Appendix ...

Страница 27: ... V2 1 1 EN 60335 1 2012 AC 2014 A11 2014 In accordance with the listed directives this product is designated with In accordance with the Ecodesign Directive 2009 125 EC and Implementing Regulations EU No 813 2013 and EU No 814 2013 the Vitoplex 100 type PV1 up to 400 kW may not be sold within the EU for the purpose of generating space heating and domestic hot water A sale is subject to the proviso...

Страница 28: ... Order BImSchV NOx limits according to paragraph 6 1 Flue gas loss of no more than 9 according to paragraph 10 1 Standard seasonal efficiency to DIN of at least 94 in accordance with paragraph 6 2 Allendorf 1 December 2017 Viessmann Werke GmbH Co KG Authorised signatory Reiner Jansen Head of Strategic Quality Management Certificates Manufacturer s certificate 5692701 Appendix ...

Страница 29: ...aintenance service report 23 Manufacturer s certificate 28 Mixer checking for ease of operation and tightness 12 O Operating and service documents 13 P Parts 16 S Safety equipment function checking 10 Setting of temperature controller 11 Sight glass in the boiler door cleaning 12 System Commissioning 7 Filling with water 7 Shutting down 7 Venting 7 System pressure checking 10 T Temperature control...

Страница 30: ...30 5692701 ...

Страница 31: ...31 5692701 ...

Страница 32: ... Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 5692701 Subject to technical modifications ...

Отзывы: