30
Boiler size
1
2
3
4
5
6
7
8
9
■
For natural gas
mbar
9.3
11.6
12.4
13.6
16.0
18.1
20.8
15.1
17.6
Max. pressure drop on the flue gas
side
■
For natural gas
mbar
8.0
9.8
11.5
12.1
13.9
15.4
16.7
11.7
13.0
■
For EL fuel oil
mbar
7.2
8.8
10.3
10.8
12.5
13.8
15.0
9.9
10.2
Tab. 10
Boiler type M82B
Boiler size
1
2
3
4
5
6
7
8
9
Rated heating output
■
For natural gas
MW
2.30
2.80
3.50
4.20
5.00
6.00
7.00
8.00
9.00
■
For EL fuel oil
MW
2.30
2.80
3.50
4.20
5.00
6.00
7.00
8.00
9.00
Max. pressure drop on the flue gas
side with condensing ECO
■
For natural gas
mbar
8.7
10.7
11.8
12.6
14.3
15.7
17.3
11.8
13.4
Max. pressure drop on the flue gas
side with non-condensing ECO
■
For natural gas
mbar
9.1
11.4
12.1
13.3
15.7
17.7
20.3
14.6
17.1
Max. pressure drop on the flue gas
side
■
For natural gas
mbar
7.9
9.6
11.2
11.7
13.5
14.9
16.2
11.1
12.5
■
For EL fuel oil
mbar
7.0
8.5
9.9
10.4
12.0
13.2
14.3
9.8
11.0
Tab. 11
Commissioning, inspection, maintenance
Adjusting the burner
(cont.)
6152553
Содержание M22