Switching cabinet
VITOBLOC 200
CHP switching cabinet
5
5780078
GB
1.3
Displays and measurements
The display shows actual values, targets, limits and fault/status messages.
Display of electrical parameters
1. alternator voltage (L1, L2, L3)
5. network frequency
2. mains voltage (L1, L2, L3)
6. actual cogeneration output
2. busbar voltage (L1, L2)
7. battery voltage
3. alternator current (L1, L2, L3)
8. reactive power factor
cos φ
4. alternator frequency
Display of engine parameters
1. oil pressure
4. lambda probe voltage
2. cooling water temperature
5. heating water return temperature into the block-type
thermal power plant (PT 100/2)
3. exhaust gas temperature A
6. total optional heating water return (PT 100/3)
Added potential engine parameters with modules with ANA 16
(EM-199/263, EM-238/363, EM-260/390, EM-401/549, EM-530/660)
7. engine oil temperature (PT 100/4)
10. exhaust gas temperatures B / C / D
8. mixed gas temperature (PT 100/5)
11. load pressure (optional)
9. mixed cooling water temperature (PT 100/6)
Display of fault messages
1. emergency stop
25. synchronising malfunctioning
2. minimum oil level
26. speed < 50 / pick-up defective
3. minimum cooling water pressure
27. maximum oil level
4. minimum gas pressure
28. maximum return temperature PT 100/2
5. safety temperature limiter tripped
29. maximum heating water temperature PT 100/3
6. maximum alternator winding temperature
30. maximum output exceeded
7. maximum sound hood temperature
31. reverse power (delayed to 50% output
– over
50% undelayed)
8. ventilator malfunctioning
32. power regulator malfunctioning
9. cooling water pump malfunctioning
33. lambda regulator malfunctioning
10. maximum exhaust gas counterpressure
34. alternator contact malfunctioning
11. feed switch tripped or turned off
35. ignition malfunctioning
12. external malfunction
36. oil pressure malfunctioning
13. overspeed
37. lambda starting position
14. cooling water temperature
48. knocking malfunction
15. maximum exhaust gas temperature A
54. safety shutdown
16. minimum exhaust gas temperature A
55. engine not stopped (speed > 50 Upm)
17. minimum oil pressure
56. battery low voltage
18. maximum gas pressure
57. alternator low voltage
19. heating water pump malfunctioning
58. alternator excess voltage
20. starting speed < 50 Upm
59. alternator excess current
21. ignition speed
60. alternator load unbalance
22. speed range not reached
61. sealing test / seal test malfunctioning
23. speed < 1,200 Upm
62. line protection malfunctioning
24. enabling malfunctioning
63. sensors malfunctioning
Содержание EM-100/173
Страница 26: ...Terminal assignment for the CHP module control field 26 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 27: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 27 5780078 GB ...
Страница 28: ...Terminal assignment for the CHP module control field 28 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 29: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 29 5780078 GB ...
Страница 30: ...Terminal assignment for the CHP module control field 30 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 31: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 31 5780078 GB ...
Страница 32: ...Terminal assignment for the CHP module control field 32 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 33: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 33 5780078 GB ...
Страница 35: ...Notes VITOBLOC 200 CHP switching cabinet 35 5780078 GB ...