Control system (BMS 2007)
VITOBLOC 200
CHP switching cabinet
19
5780078
GB
2.5
Parameters
The following are adjustable on level 3 (only with password):
Level 3
– parametering
1. output target
electrical active power
2. warm-up limit
cooling water temperature limit at 50% output
3. output limit
emergency shutdown if limits exceeded
4. reverse power
emergency shutdown with negative output limit
5. output ramp higher/lower
output target change in kW/s
6. monitoring power regulator
emergency shutdown with target value deviation after time
7. power regulator dead band
regular dead band in kW
8. knocking
output reduction with digital knocking input
9. lambda probe target value
10. lambda regulation impulse time
impulse duration open/close command
11. lambda regulation dead time
interpulse period between the open/close commands
12. lambda regulator dead band
regular dead band
13. monitoring lambda regulator
emergency shutdown with target value deviation after time
14. maximum cooling water
emergency shutdown if limits exceeded
15. maximum exhaust gas temperature
emergency shutdown if limits exceeded
16. minimum exhaust gas temperature
emergency shutdown if below limits
17. exhaust gas temperature release
maximum release if below limit after exhaust gas
18. battery low voltage
emergency shutdown if below limits
19. starter limit
speed limit for starter off
20. overspeed
emergency shutdown if limits exceeded
21. after-run time / start-up time ventilator
after-run time or start-up time of ventilator
22. after-run time / start-up time cooling water
pump
after-run time or start-up time of cooling water pump
23. minimum temperature controller, target
value
minimum opening, spare target
24. Kp/Tn temperature controller
Kp and Tn value input
25. governor 0=10
–0 V, 1=0–5 V
target controller specification 10
–0 V (GAC) or 0–5 V (Heinzmann)
26. spare
27. excess alternator current
emergency shutdown if limits exceeded
28. alternator load imbalance
emergency shutdown if limits exceeded
29. low alternator voltage
emergency shutdown if below limits
30. excess alternator voltage
emergency shutdown if limits exceeded
31. temperature PT 100/2
emergency shutdown if limits exceeded
32. temperature PT 100/3
emergency shutdown if limits exceeded
33. minimum oil pressure
emergency shutdown if below limits
34. offset lambda probe
potential adjustment if there are analog parameter differences
35. offset NiCrNi
potential adjustment if there are analog parameter differences
36. offset engine cooling water
potential adjustment if there are analog parameter differences
37. offset temperature PT 100/2
potential adjustment if there are analog parameter differences
38. offset temperature PT 100/3
potential adjustment if there are analog parameter differences
39. offset oil pressure
potential adjustment if there are analog parameter differences
40. offset battery voltage
potential adjustment if there are analog parameter differences
Tab. 21 Parameter, Part 1
– level 3
Содержание EM-100/173
Страница 26: ...Terminal assignment for the CHP module control field 26 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 27: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 27 5780078 GB ...
Страница 28: ...Terminal assignment for the CHP module control field 28 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 29: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 29 5780078 GB ...
Страница 30: ...Terminal assignment for the CHP module control field 30 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 31: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 31 5780078 GB ...
Страница 32: ...Terminal assignment for the CHP module control field 32 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 33: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 33 5780078 GB ...
Страница 35: ...Notes VITOBLOC 200 CHP switching cabinet 35 5780078 GB ...