Control system (BMS 2007)
10
CHP switching cabinet
VITOBLOC 200
5780078
GB
Tab. 9
Assignment of function keys , Part 1
– F1-F6
F1 - stop
The stop button runs down and stops the cogeneration module secured from all modes.
F2 - engine
speed
oil pressure
cooling water temperature
lambda probe voltage
exhaust gas temperature
battery voltage
F3 - automatic
The automatic button passes the operation of the cogeneration module to module control.
F4 - U-I (voltage and current values)
mains voltage
active power
network frequency
cos
alternator voltage
alternator frequency
alternator current
F5 - menu
When you select the F5 key, you are in the menu and the numerical keypad enables you to call up the functions
below:
password
keying in the password, date and time
controller
keying in the target value and showing the actual value for the temperature controller
release
module, select and deselect parameters after release temperature / modulation (optional)
com
activating the interface for the printer, 3964 passive, 3964 active
option
other optional submenus
version
checking the module serial number and software version
status
print-out of the status of the present operational values
parameter
print-out of the parameters set in level 3 and EVU level
Service
submenu for service and fault archive
F6 - level
When you key in a password for each level, you can reach the following levels with the F6 key:
level 2
manual operation: manual mode, start, alternator release, speed or output higher/lower,
manual cooling water pump operation, manual ventilator operation and min-max values
level 3
parametering: showing and changing all module parameters
EVU level
showing and changing all EVU parameters
FACTORY level
showing and changing all factory parameters
Specific passwords are only issued to authorised persons (such as start-up personnel, service personnel or
operators).
Содержание EM-100/173
Страница 26: ...Terminal assignment for the CHP module control field 26 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 27: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 27 5780078 GB ...
Страница 28: ...Terminal assignment for the CHP module control field 28 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 29: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 29 5780078 GB ...
Страница 30: ...Terminal assignment for the CHP module control field 30 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 31: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 31 5780078 GB ...
Страница 32: ...Terminal assignment for the CHP module control field 32 CHP switching cabinet VITOBLOC 200 5780078 GB ...
Страница 33: ...Terminal assignment for the CHP module control field VITOBLOC 200 CHP switching cabinet 33 5780078 GB ...
Страница 35: ...Notes VITOBLOC 200 CHP switching cabinet 35 5780078 GB ...