Electrical Connections
12
Sensors
Supply temperature sensor (strap-on sensor)
Mount the supply temperature sensor
downstream from the heating circuit
pump on the heating supply pipe at a
distance of approx. 3 to 5 ft /
1 to 1.5 m from the mixing valve.
Where plastic pipes are used, mount the
sensor on an intermediate metal pipe
section. It is not necessary to use heat
conductive paste.
If a pressure-activated bypass valve
is
installed, mount the sensor
on the
supply pipe immediately after the bypass
valve.
1.
Thoroughly clean the heating supply
pipe until metallically bright.
2.
Open the case
of the sensor with a
screwdriver.
3.
Place the perforated mounting strap
(supplied inside the sensor case) on
the tensioning screw
, run it around
the supply pipe
and place back on
the tensioning screw; tighten the
tensioning screw.
4.
Close the sensor case.
The sensor must not be insulated.
5.
If the outdoor temperature sensor
or a room temperature sensor is
to be connected, go to page 13.
Otherwise, insert connector
in socket “X14” in the terminal
compartment (see page 10); install
strain relief clamp.
5167
137
Fig. 5
Supply temperature sensor
IMPORTANT
Fig. 6
Installing the supply temperature sensor downstream from the bypass valve
Fig. 7
Opening the case
Fig. 8
Opening the supply temperature sensor and fastening with perforated mounting strap
IMPORTANT
Содержание Dekamatik-HK1
Страница 23: ...Appendix 23 Notes 5167 137...