12
A
B
C
A
A
A
Fig. 4
1.
Undo the fixing screws in top panels
A
. Remove
the panels.
2.
Open the thermal insulation of the heat exchanger
module until connecting flange
C
is freely accessi-
ble.
3.
Check connecting flange
C
, sensor well
B
and
all connections on the heating water side for tight-
ness.
4.
Close the thermal insulation of the heat exchanger
module.
5.
Position the top panels and secure with screws.
Note
The gaskets can also be checked under full load with
an inspection mirror. If required, remove the thermal
insulation components.
Checking the function of the safety equipment
Check safety valves, water level and pressure limiter in
accordance with manufacturer's details.
Checking the pressure switch function
Installation instructions, pressure switch set
Commissioning, inspection, maintenance
Checking all connections and the sensor well on…
(cont.)
5692910