background image

13

5600 336 - 04 

CombiPLUS Kit for Vitodens 100-W, WB1B  Quick Start 

Installation

 

Adding PRV and Label

Installing the PRV 

and tee 

to the 

CombiPLUS 

and label 

S

 to the boiler.

Note: 

The system must be leak tested. 

 

   Refer to the boiler Installation  

 

 

   Instructions.

The DHW pressure relief valve is designed 

to relieve excessive pressure in the system, 

produced during domestic hot water heating.
Model: Watts No. 3L

Size: ¾” NPT

Max. Operating Pressure: 150 psig

Input Rating: 200 MBH

The installation of the DHW pressure relief 

valve must be in accordance with local codes. 

The DHW pressure relief valve must be installed 

in the domestic hot water supply by a heating 

contractor. If local codes require a different 

relief valve, substitute the valve supplied by the 

manufacturer. The heat exchanger is approved 

for a max. operating pressure of 150 psig.

The DHW pressure relief valve must be 

installed in vertical position in the domestic hot 

water supply as close to the CombiPLUS heat 

exchanger as possible. Drain pipe (of same 

diameter as valve outlet) must be routed to safe 

place of disposal, and must be installed with a 

downward slope from the valve.

Do not install a shutoff valve between the DHW 

pressure relief valve and the heat exchanger, or 

in the drain pipe.

1

 Install the 150 psi PRV 

and tee 

to the installed field supplied piping from  

 the 

CombiPLUS 

A

.

2

 Apply the scald danger label 

as    

 shown.

Note: 

This label must be installed as required 

 

  by national code.

1

2

Heating 

Circuit 

Supply

DCW

DHW

Heating 

Circuit 

Return

Boiler 

Supply

Boiler 

Return

S

P

O

A

Содержание CombiPLUS Kit

Страница 1: ...B series boilers This Installation Quick Start Guide is not intended to replace the actual Installation Instructions for the Vitodens 100 W WB1B Series Boilers and the CombiPLUS Kit For complete instructions follow the Installation Instructions that are included with the boiler Vitodens 100 W WB1B with CombiPLUS Kit installed Please file in Service Binder ...

Страница 2: ...itting x2 C Locking clip x2 D Heating circuit gasket x2 E DHW gasket x2 F c Heating circuit adaptor x2 G b DHW adaptor x2 H Flow restrictor WB1B 26 only I Lag bolt x4 J a plain washer x4 K Anchor x4 L 7 flex pipe x2 N c Adaptor x2 O c tee P c PRV 150 psi Q Control cable R Pump cable S Scald danger label T CombiPLUS mounting template U Conduit Clip x2 V 10 Anchor x2 W 10 Wood Screw x2 ...

Страница 3: ...ion procedures 1 Align and mark the wall mounting bracket using the supplied boiler mounting template Install the mounting bracket to the wall and ensure the bracket is level Use the supplied lag bolts and anchors if required and ensure the bracket is securely fastened to the wall 2 Hang the boiler on the installed wall mounting bracket 3 Install supplied boiler fittings as shown 3 1 2 mm ...

Страница 4: ...cked in place See page 13 for water flow directions in piping and fittings Note Use a two hand wrench method when tightening fittings or piping onto the boiler and CombiPLUS connectors Use one wrench to prevent the boiler and CombiPLUS pipes from twisting and the second wrench to tighten the fitting or piping Failure to support the boiler or CombiPLUS connections could damage the boiler and or the...

Страница 5: ...ht up ensure not to damage the gasket and set aside Remove the factory installed 14L min flow restrictor a small flat screw driver maybe required to unseat the restrictor and discard 2 Install the new flow restrictor H for the WB1B 26 model only supplied with the installation fittings Color Specification WB1B 26 black on white 10L min WB1B 35 brown on white 14L min 3 Reinstall the flow tube cap en...

Страница 6: ...ust the template to the boiler in this position when connecting the 7 flex piping 2 Drill a hole through the top mounting hole as shown on the template x2 Drill a hole in the centre of the slot as shown on the template x2 Remove the template 3 Install the supplied anchors K into the wall if required 4 Install the supplied washers J on to the lag bolts I Install the lag bolts washers into the wall ...

Страница 7: ...al length of the 7 flex pipe after bending is 6b a Slide the CombiPLUS A up and install the flex pipes L to the extension fittings of the CombiPLUS A 2 Tighten the two lag bolts located in the CombiPLUS A mounting bracket slots Install the supplied washers J on to the lag bolts I Install the lag bolts washers through the upper mounting holes of the CombiPLUS A mounting bracket and into the wall an...

Страница 8: ...e control cable Q through one knock out and the pump cable R through the other Note There are optional knock outs on the front left side of the CombiPLUS A if required Secure the cables inside the CombiPLUS A using the locknuts provided 2 Connect the electrical connectors in the CombiPLUS A as shown Installation 1 2 A Q R A A Pump connection Diverting valve motor connection Flow sensor connection ...

Страница 9: ... 1 Loosen the boiler housing captive screws located at the bottom front of the boiler Remove the cover by pulling straight out from the boiler and set aside 2 Release and hold the boiler control locks located on both sides of the boiler and rotate forward and down 3 Release the four captive screws on the power pump module cover by rotating them 90 degrees with a Phillips screw driver Set the cover...

Страница 10: ...ule and discard 2 Remove the jumper cable from terminal block X4 terminals 3 4 room thermostat connection of the power pump module and discard for room thermostat connection only 3 Remove the second and fourth hole plug from the base of the power pump module and discard Note Once the CombiPLUS is installed and the jumper pin is removed if not programmed for use with the CombiPLUS the boiler will p...

Страница 11: ...er pump line of terminal block X3 as shown Connect the green yellow ground wire to terminal block X2 any open terminal 3 The control cable Q has two connectors Connect the DHW temperature sensor flow sensor five pin connector to terminal plugin X7 Connect the diverter valve six pin connector to terminal plugin X10 Note For additional wiring details see the wiring diagram 4 Install the supplied anc...

Страница 12: ...90 degrees with a Phillips screw driver 2 Rotate the boiler controls up and in Ensure that the locking clips are engaged 3 Install the boiler cover by inserting it straight on from the front 4 Tighten the boiler housing captive screws located at the bottom front of the boiler 5 Install the CombiPLUS A cover by inserting it straight on from the front 6 Using a Phillips screw driver install and tigh...

Страница 13: ... codes require a different relief valve substitute the valve supplied by the manufacturer The heat exchanger is approved for a max operating pressure of 150 psig The DHW pressure relief valve must be installed in vertical position in the domestic hot water supply as close to the CombiPLUS heat exchanger as possible Drain pipe of same diameter as valve outlet must be routed to safe place of disposa...

Страница 14: ...r central position SERV will appear on the screen Note If one or both of the rotary selector dials are already in the central position take it or them out of the central position and then simultaneously turn both rotary selectors back to the central position 3 Turn the rotary selector fully to the right will appear on the display 4 Adjust the control by turning the rotary selector tr The display s...

Страница 15: ...15 5600 336 04 CombiPLUS Kit for Vitodens 100 W WB1B Quick Start Wiring Diagram Electrical ...

Страница 16: ...CombiPLUS Kit for Vitodens 100 W WB1B Quick Start 5600 336 04 Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper ...

Отзывы: