79
Gas boiler, category II
2ELL3P
Rated boiler heating
output
P
min
-P
max
P
min
-P
max
P
min
-P
max
T
V
/T
R
= 50/30 °C
kW
80(100
*2
)-400 100(125
*2
)-500 124(155
*2
)-620
T
V
/T
R
= 80/60 °C
kW
74(93
*2
)-370
92(115
*2
)-460 115(144
*2
)-575
Rated heat input
kW
Q
min
-Q
max
(H
i
)
Q
min
-Q
max
(H
i
)
Q
min
-Q
max
(H
i
)
76(95
*2
)-381
95(119
*2
)-474 119(148
*2
)-593
CE designation
CE-0085BQ0021
Connection values
*3
Relative to the max. load
with
■ Natural gas E
m
3
/h
8.1-40.4
10.0-50.2
12.5-62.7
■ Natural gas LL
m
3
/h
9.4-46.9
11.7-58.3
14.6-72.9
■ LPG P
kg/h
7.4-29.6
9.2-36.8
11.5-46.1
Burner type
CM2
Voltage
V
230
Frequency
Hz
50
Power consumption
W
69-576
66-655
74-835
Burner and control unit
Modulation range
%
20-100 (25-100
*2
)
*2
Only with LPG P.
*3
The connection values are only for reference (e.g. in the gas contract application)
or to estimate the volumetric supplementary check of the settings.
Due to the factory settings, the gas pressure must not be altered from these values.
Reference: 15 °C, 1013 mbar