42
5773 597 - 04
Vitocrossal 200, CM2 400, 500 and 620 Installation
Component Installation Guide
Flashing and storm collar installation
Flashings and storm collars are field supplied.
Flashings and storm collars suitable for Type B vent
materials (or better) may be used.
To obtain flashings and storm collars, please contact
your local vent material supplier. Follow the installation
instructions supplied by the special venting manufacturer.
Vent Termination Location Requirements - Vertical
WARNING
Vent termination must be at least 12 in. (305 mm)
above the anticipated snow level (consult your local
building authorities or local weather office). Locate
vent termination in such a way that it cannot be
blocked by snow.
IMPORTANT
A vent used in a special venting system with positive
vent pressure and passing through a roof shall extend at
least 18 in. (450 mm) above the highest point where it
passes through the roof and any other obstruction within
a horizontal distance of 18 in. (450 mm).
The special vent system shall not be routed into, through,
or within any other vent such as an existing masonry or
factory-built chimney.
A masonry chimney flue may be used to route the venting
system only if no other appliance is vented in the same flue.
For flat roof applications
The vent must be installed observing local regulations
in addition to National Codes, CAN/CSA-B149.1 or 2
(for installations in Canada) or ANSI-Z223.1 or NFPA 54
(for installations in the U.S.A.).
For sloped roof applications
with distance b greater than 18 in. (450 mm)
For sloped roof applications
with distance b less than 18 in. (450 mm)
a minimum 18 in. (450 mm)
b <18 in. (450 mm)
Venting