109
Parameter
Code
Delivered condi-
tion
Commis-
sioning
Heating water buffer cylinder
Enable buffer cylinder / low loss header
7200
0
Temp. in operating status fixed value for
buffer cyl
7202
500 (
≙
50 °C)
Hysteresis temperature heating buffer
cylinder
7203
50 (
≙
5 K)
Max. temperature buffer cylinder
7204
600 (
≙
60 °C)
Temp. limit op. status fixed value for buf-
fer cylinder
7208
100 (
≙
10 °C)
Heating circuit 1
Standard room temperature
2000
200 (
≙
20 °C)
Reduced room temperature
2001
160 (
≙
16 °C)
Remote control
2003
0
Heating curve level
2006
0 (
≙
0 K)
Heating curve slope
2007
6 (
≙
0.6)
Influence room temperature hook-up
200A
10
Room temperature hook-up
200B
3
Max. flow temperature heating circuit
200E
400 (
≙
40 °C)
Room temperature in party mode
2022
200 (
≙
20 °C)
Heating circuit 2
Standard room temperature
3000
200 (
≙
20 °C)
Reduced room temperature
3001
200 (
≙
20 °C)
Remote control
3003
0
Heating curve level
3006
0 (
≙
0 K)
Heating curve slope
3007
6 (
≙
0.6)
Influence room temperature hook-up
300A
10
Room temperature hook-up
300B
3
Max. flow temperature heating circuit
300E
400 (
≙
40 °C)
Room temperature in party mode
3022
160 (
≙
16 °C)
Cooling
Cooling function
7100
0
Cooling circuit
7101
1
Set room temperature separate cooling
circuit
7102
200 (
≙
20 °C)
Min. flow temperature cooling
7103
100 (
≙
10 °C)
Influence room temperature hook-up
cooling circuit
7104
0
Cooling curve level
7110
0 (
≙
0 K)
Commissioning/service reports
Control parameters report
(cont.)
5601 574 GB
Service
Содержание BWT 221.A06
Страница 18: ...18 Removing the cylinder module 3 1 5 4 2x 2 Installation sequence Siting the heat pump cont 5601 574 GB ...
Страница 19: ...19 6 8 F6 X3 sG sH lJ aYH 7 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Страница 20: ...20 aCH 10 9 Installation sequence Siting the heat pump cont 5601 574 GB ...
Страница 21: ...21 12 13 17 X20 14 2x 11 2x 15 16 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Страница 22: ...22 4x 18 21 4x 6x 20 2x 19 Installation sequence Siting the heat pump cont 5601 574 GB ...
Страница 23: ...23 25 2x 24 4x 22 23 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Страница 28: ...28 4 1 3 2 Installation sequence Siting the heat pump cont 5601 574 GB ...
Страница 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 574 GB Service ...
Страница 72: ...72 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 574 GB ...
Страница 105: ...105 0006 0005 0004 0001 0003 0002 0002 0003 Parts lists type BWT M 230 V Fitting set cont 5601 574 GB Service ...
Страница 122: ...122 5601 574 GB ...
Страница 123: ...123 5601 574 GB ...