34
Terminals
Function
Explanation
38KF8/11;14
Dry cooler
Floating N/O contact:
■
Closed: dry cooler demand
■
Open: no demand
Connection values
■
Max. voltage:
250 V
∼
■
Max. switching current:
4 A (AC1)
38X6
Shut-off valve, dry cooler
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A
40X5
Shut-off valve, residual heat
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A
36X0
Diverter valve 1, 3-way diverter valve,
cooling mode
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A
36X2
Diverter valve 2, 2-way shut-off valve,
source
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A
36X3
Diverter valve
Cooling circuit 1
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A
36X5
Diverter valve
Cooling circuit 2
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A
36X7
Diverter valve
Cooling circuit 3
Connection values
■
Voltage:
24 VDC
■
Max. switching current:
4 A