background image

Installation and service instructions

for contractors

Viesmann

Vitocal 300-G Pro SPS
Type  BW 301.CS090 to 302.CS230

, 82.8 to 296.0 kW

Heat pump, single and two-stage

For applicability, see the last page

VITOCAL 300-G PRO SPS

5789 986 GB

9/2016

Please keep safe.

Содержание BW 30 .CS Series

Страница 1: ...ructions for contractors Viesmann Vitocal 300 G Pro SPS Type BW 301 CS090 to 302 CS230 82 8 to 296 0 kW Heat pump single and two stage For applicability see the last page VITOCAL 300 G PRO SPS 5789 98...

Страница 2: ...ant trade associations All relevant safety regulations as defined by DIN EN DVGW VDE and locally applicable standards a NORM EN and VE c SEV SUVA SVTI SWKI and SVGW Working on the system Isolate the s...

Страница 3: ...with the system can compromise its function Installing non authorised components and making non approved modifications or con versions can compromise safety and may inva lidate our warranty For repla...

Страница 4: ...connections 24 Connecting the Vitocal 300 G 25 Fitting the Victaulic couplings 26 Connecting the primary circuit 27 Connecting the secondary circuit 27 Electrical connections 28 Routing cables to the...

Страница 5: ...issioning service reports Commissioning report 58 10 Specification Specification Vitocal 300 G 61 11 Appendix Heat pump commissioning request 65 12 Final decommissioning Dismantling disposal 66 13 Cer...

Страница 6: ...X X X X X Installation X X X Commission ing X X X X Operation X X Maintenance repair shut down X X X X X Dismantling removal col lection X X X X X Disposal X X X Electrical connections Danger Electrom...

Страница 7: ...hreatening crushing or break ages if they fall or are dropped Use suitable ropes slings and lifting gear when installing dismantling compressors and heat exchangers for example Wear appropriate protec...

Страница 8: ...ehind sharp edges from the metal retaining tabs that can lead to life threatening injuries Finish and seal the edges appropriately before installation Note Damage to the surfaces of the casing can lea...

Страница 9: ...or In conjunction with a tool Clean the sur face Dispose of component correctly Dispose of component at a suitable collec tion point Do not dispose of component in domestic waste The steps in connect...

Страница 10: ...y by authorised and trained personnel Product information Vitocal 300 G Pro SPS Heat pump Vitocal 300 G Pro SPS type BW Medium Brine water Single stage heat pumps 301 CS090 301 CS120 2 stage heat pump...

Страница 11: ...damage on the delivery note and notify the haulage contractor Lifting gear such as slings and cross beams must be provided on site The lifting capacity of each sling and that of the cross beam must be...

Страница 12: ...tion e g 2 or 3 layers of corrugated cardboard D Cross beam to relieve the load on the frame Note Lifting with belt straps is only permitted without the side front or back panels fitted Handling by fo...

Страница 13: ...note Overloading the floor can result in damage to the building structure Observe the permissible floor load Take the weight of the appliance into account Weight Type Weight in kg BW 301 CS090 770 BW...

Страница 14: ...ll clearance 80 mm B When using hydraulic connection accessories connection set and Victaulic flange adaptor set 2 or 3 1000 mm On site hydraulic connections 600 mm C Clearances for installation and m...

Страница 15: ...n screed C Top edge unfinished floor D Impact sound insulation as per regulations E Pressure tested sound insulation layer approx 10 to 20 mm F Heat pump Pressure points of the adjustable heat pump fe...

Страница 16: ...e BW 301 CS090 to BW 301 CS120 BW 302 CS090 and BW 302 CS110 850 1343 1650 911 1241 644 436 1126 368 343 200 Fig 8 A flow primary circuit inlet Victaulic 3 DN 80 B flow secondary circuit outlet Victau...

Страница 17: ...ctaulic 2 DN 65 E Low voltage 50 V F Power supply 230 V 50 Hz G Power supply 400 V 50 Hz Note The width of the heat pump is given with and without side panels The dimensions without side panels are th...

Страница 18: ...ic connections General hydraulic scheme DHW Fig 10 Black lines master circuit grey lines slave circuit DHW circulation Preparing for installation Hydraulic connection requirements cont 5789 986 GB Ins...

Страница 19: ...ircuit 9 Expansion vessel primary circuit residual heat circuit qP Geothermal probe manifold qQ Safety assembly primary circuit qW Pressure switch primary circuit qE Frost stat qR System separation gr...

Страница 20: ...trol requires additional con tactor w E 3 way diverter valve heating cooling w R Heating circuit pump HC2 w T 3 way mixer e P Underfloor heating circuit cooling circuit M3 e Q Flow temperature sensor...

Страница 21: ...21 Levelling the heat pump Fig 11 Site and level the heat pump horizontally as described on page 13 onwards Installation sequence Siting the heat pump 5789 986 GB Installation...

Страница 22: ...ort brackets are not removed they cause vibrations and excessive noise Remove all 4 transport brackets fully from below and dispose of them correctly Fig 12 A Transport locking screws Installation seq...

Страница 23: ...de panels and kicking plates Note After fitting the back panel make the hydraulic and electrical connections See following chapter 1 2 3 3 4 2x 6x 5 Fig 13 Installation sequence Siting the heat pump c...

Страница 24: ...3 DN 80 B flow secondary circuit outlet Victaulic 2 DN 65 C return primary circuit outlet Victaulic 3 DN 80 D return secondary circuit inlet Victaulic 2 DN 65 E Low voltage 50 V F Power supply 230 V...

Страница 25: ...pling 2 secondary circuit C Flexible connection pipe 3 primary circuit with anti vibration elements D Flexible connection pipe 2 secondary circuit with anti vibration elements E Hydraulic line fixings...

Страница 26: ...line fixings Fitting the Victaulic couplings Fig 17 1 Clean all Victaulic connections 2 Open Victaulic coupling B around 1 cm 3 Push Victaulic coupling B with inserted gasket as far as it will go onto...

Страница 27: ...seated correctly Make line entries airtight 4 Insulate primary lines inside the building with ther mally insulating and vapour diffusion proof materi als 5 Fill the primary circuit with Viessmann heat...

Страница 28: ...ult e g if a wire becomes detached the wires cannot drift into the adjacent voltage area When routing on site power cables observe the loca tion of the cable entries into the appliance through the bac...

Страница 29: ...le wire ferrule Wiring chamber front Fig 19 Note Diagram without terminal covers see also page 56 A Power supply power circuit compressor 3 x 400 V 50 Hz with ON OFF switch B Circuit breaker LV HRC fu...

Страница 30: ...CD3OEM C Contactors for primary pump secondary pump and options D Terminal strip for external heat pump components E Relay control options F Terminal strip for internal heat pump components Installati...

Страница 31: ...values Max voltage 250 V Max switching current 4 A AC1 Circuit protection from load fuse 5FC1 observe the maximum total current of 16 A Terminals Function Explanation 13X0 Circulation pump evaporator...

Страница 32: ...hing current 9 A AC3 25X1 Circulation pump external heat source Connection values Max output 4000 W 2200 W Voltage 400 V 230 V Max switching current 9 A AC3 40X0 Circulation pump residual heat Connect...

Страница 33: ...xing valve external heat source Connection values Max output 180 VA Voltage 24 VAC DC 0 10 V Terminals Function Explanation 22X0 Diverter valve DHW heating Connection values Voltage 24 VDC Max switchi...

Страница 34: ...er valve 1 3 way diverter valve cooling mode Connection values Voltage 24 VDC Max switching current 4 A 36X2 Diverter valve 2 2 way shut off valve source Connection values Voltage 24 VDC Max switching...

Страница 35: ...ations Multi stage enabling input 1 one stage 19X6 External multi stage enabling input 2 Function depends on the configuration For complete third party control without set value External demand 2 For...

Страница 36: ...ppliance All sensor and signal leads 0 10 V must be shielded with copper braiding and have a mini mum cross section of 0 5 mm2 Specified lead type CV Sensors internal Terminals Analogue inputs and out...

Страница 37: ...m Danger Incorrectly executed electrical installations can result in injuries from electrical current and dam age to the appliance Connect the power supply and implement all safety measures e g RCD ci...

Страница 38: ...routing in the vicinity of heating pipes or encapsulated routing the cross sections and max cable lengths must be recalculated on site Power circuit 400 V on site control circuit 230 V factory fitted...

Страница 39: ...abled Note Observe the technical connection conditions of the rel evant power supply utility Electronic soft starter type SMC Electronic soft starter functions Monitoring the compressor mains feed Red...

Страница 40: ...SS OPEN LOAD 5 PHASE IMBALANCE 6 SHORTED SCR 7 TEST L1 L2 L3 T1 T2 T3 Fig 21 Number of flashes 1 Overload 2 Excess temperature 3 Phase reversal 4 Phase loss motor not connected 5 Phase asymmetry 6 Sho...

Страница 41: ...the programming unit into place in the open ing and check for firm seating Securely lean the front panel against the heat pump Closing the heat pump Danger The absence of component earthing can resul...

Страница 42: ...conductors been fitted Have all cable entries been correctly applied and sealed against moisture ingress Do all hydraulic connections have airtight sealing and insulation with thermal and vapour diffu...

Страница 43: ...44 5 Filling and venting on the secondary side 45 6 Checking expansion vessels and primary circuit secondary circuit pressure 45 7 Commissioning the system 45 8 Checking the electronic flow switch typ...

Страница 44: ...on page 58 onwards Checking the refrigerant circuit for leaks Check the floor area valves and all visible solder joints for traces of oil Note Traces of oil indicate a leak in the refrigerant circuit...

Страница 45: ...p with water if required Minimum system pressure 0 8 bar 80 kPa Permiss operating pressure 6 bar 0 6 MPa Checking expansion vessels and primary circuit secondary circuit pressure Observe engineering i...

Страница 46: ...her than nominal flow rate If necessary carry out an operating display adjustment high flow balancing see below for example if a circulation pump had to be sized for higher flow rates LED 0 flashes gr...

Страница 47: ...and hold for around 5 s until LED 9 flashes 3 Release Fitting the top panel and front panel closing the heat pump See page 41 Instructing the system user The system installer should hand the operating...

Страница 48: ...will go Hydraulic line is touching the heat pump casing back panel Hydraulic line not connected free of load and torque stress Anti vibration elements for hydraulic connection are missing Connection l...

Страница 49: ...e and ensure it cannot fall over 4 Carefully remove the top panel see page 42 Overview of electrical components See page 29 onwards Overview of internal components Vitocal 300 G Fig 25 Example type BW...

Страница 50: ...he heat pump at the on site drain valve on the primary secondary side Checking sensors Sensor Test element Connection installation position Outside temperature sensor Flow temperature sensor secondary...

Страница 51: ...pecification Power circuit fuse system components see sepa rate Connection and wiring diagram Danger Contact with live components can lead to seri ous injury from electric current Before working on th...

Страница 52: ...52 Repairs Checking fuses cont 5789 986 GB Maintenance...

Страница 53: ...53 The following details are required when ordering parts Serial no see type plate Position number of the part from this parts list Parts lists Ordering parts 5789 986 GB Components...

Страница 54: ...2 0014 0001 0026 0024 0004 0006 0007 0007 0016 0011 0011 0012 0015 0001 0010 0021 0018 0019 0020 0003 0009 0008 0022 0022 0023 0027 0005 0013 0017 0025 Fig 27 Parts lists Parts section 1 5789 986 GB C...

Страница 55: ...bly 0012 Dryer bracket 0013 Temperature sensor Pt1000 2 or 4 m 0014 Oil compensation line 0015 Sight glass for soldering 0016 Electronic expansion valve 0017 Sensor well with gasket 0018 Motor overloa...

Страница 56: ...33 0031 0033 0031 0032 3x 0032 0034 0034 0035 0033 0039 0036 0038 0037 0043 0042 0047 4x 0052 0049 0050 0051 0053 0055 0054 0046 0045 17x 17x 11x 0048 0049 0050 0051 0044 0041 0040 0040 0044 0044 0049...

Страница 57: ...tension module 0038 SPS connector 0039 Ethernet switch 0040 Circuit breaker 0041 Circuit breaker 0042 Circuit breaker 0043 Circuit breaker 0044 Neutral conductor isolator 0045 Base for relay 0046 Rela...

Страница 58: ...Overheating set value Config heat pump param eters Evaporator pump advance runtime primary circuit Config heat pump param eters Fault primary circuit flow response delay System groundwater heat sourc...

Страница 59: ...ng circuit 1 room standard temperature day Heating circuit 2 room standard temperature day Heating circuit 3 room standard temperature day System heating circuits heating circuit1 curve night standard...

Страница 60: ...change service password required Group 1 cooling factor room flow temperature Group 2 cooling factor room flow temperature Group 3 cooling factor room flow temperature System cold water set val ue fi...

Страница 61: ...flow rate kPa 6 0 6 5 7 5 7 6 9 0 9 3 10 0 Max flow temperature C 20 20 20 20 20 20 20 Min flow temperature C 5 5 5 5 5 5 5 Min flow temperature ice store at nominal flow rate C 10 10 10 10 10 10 10...

Страница 62: ...7 7 Heating water secondary circuit Content l 18 4 23 1 18 4 23 1 28 7 35 1 50 3 Nominal flow rate m3 h 20 0 25 7 19 0 24 9 31 1 40 2 51 3 Pressure drop at nominal flow rate 5 K kPa 25 0 28 0 22 0 26...

Страница 63: ...0 20 20 20 Max power consumption stages 1 and 2 W 45 45 45 45 45 Protection class IP rating IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 Refrigerant circuit Refrigerant R410A R410A R410A R410A R410A R410...

Страница 64: ...914 2 weighted to tal sound power level at B0 3 K W35 5 K At rated heating output dB A 63 67 57 63 66 65 69 ErP SCOP LT 5 16 5 22 5 13 5 1 5 1 5 17 5 23 etas LT 198 201 197 196 196 199 201 SCOP HT 3 6...

Страница 65: ...uits fully installed and filled Electrical installation completed Hydraulic lines fully thermally insulated All windows and external doors airtight Geothermal probes well and connection lines fully in...

Страница 66: ...t be carried out by type The dismantling of refrigeration systems may only be carried out by qualified professio nals If permissible components marked with the Green Dot symbol can be disposed of via...

Страница 67: ...12 EN 61 000 6 4 2011 09 EN 50 090 2 2 2007 11 EN 62233 2008 11 EN 55011 2011 EN ISO 12100 2011 03 EN 60 335 2 40 2014 01 EN 292 1991 11 EN 60 335 1 with A1 2012 10 EN 378 2012 08 EN 61 000 6 2 2011 0...

Страница 68: ...tandards DIN 8901 2002 12 EN 61 000 6 4 2011 09 EN 50 090 2 2 2007 11 EN 62233 2008 11 EN 55011 2011 EN ISO 12100 2011 03 EN 60 335 2 40 2014 01 EN 292 1991 11 EN 60 335 1 with A1 2012 10 EN 378 2012...

Страница 69: ...cuit Curve 50 Flow temperature sensor secondary circuit Curve 50 Fuses checking 51 H Heat pump closing 41 47 Heat pump draining 50 Heat pump opening 44 Heat pump levelling 21 Heat pump siting 21 Heat...

Страница 70: ...ressure switch 49 Schrader valve 50 Seal ring replacement 44 45 Secondary circuit filling 45 Secondary circuit filling and venting 45 Secondary circuit connection 27 Sensors 49 Sensors checking 50 Sig...

Страница 71: ...71 5789 986 GB...

Страница 72: ...essmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0...