102
Gas condensing boiler
Gas boiler, type B and C, cate-
gory II
2N3P
Type
B1HF
Rated heating output range (de-
tails to EN 15502)
T
F
/T
R
= 50/30 °C
Natural gas
kW
3.2 (5.7
*4
) -
11.0
3,2 (5,7)- 19,0 3,2 (5,7) - 25,0
3,2 (5,7) - 32,0
LPG
kW
3,2 - 11,0
3,2 - 19,0
3,2 - 25,0
3,2 - 32,0
T
F
/T
R
= 80/60 °C
Natural gas
kW
2,9 (5,2) - 10,1 2,9 (5,2) - 17,5 2,9 (5,2) - 23,0
2,9 (5,2) - 29,3
LPG
kW
2,9 - 10,1
2,9 - 17,5
2,9 - 23,0
2,9 - 29,3
Rated heating output for DHW
heating
Natural gas
kW
2,9 (5,2) - 17,5 2,9 (5,2) - 17,5 2,9 (5,2)- 23,0
2,9 (5,2) - 29,3
LPG
kW
2,9 - 17,5
2,9 - 17,5
2,9 - 23,0
2,9 - 29,3
Rated heat input (Qn)
Erdgas
kW
3,0 (5,3) - 10,3 3,0 (5,3) - 17,8 3,0 (5,3) - 23,4
3,0 (5,3) - 29,9
Flüssiggas
kW
3,0 - 10,3
3,0 - 17,8
3,0 - 23,4
3,0 - 29,9
Rated heat input for DHW heat-
ing (Qnw)
Natural gas
kW
3,0 (5,3) - 17,8 3,0 (5,3) - 17,8 3,0 (5,3) - 23,4
3,0 (5,3) - 29,9
LPG
kW
3,0 - 17,8
3,0 - 17,8
3,0 - 23,4
3,0 - 29,9
Product ID
CE-0085DL0217
IP rating
to EN 60529
IPX4 gemäß EN 60529
NO
x
6
6
6
6
Gas supply pressure
Natural gas
mbar
kPa
20
2
20
2
20
2
20
2
LPG
mbar
kPa
50
5
50
5
50
5
50
5
Max. permiss. gas supply pres-
sure
*2
Natural gas
mbar
kPa
13 - 25,0
1,3 - 2,5
13 - 25,0
1,3 - 2,5
13 - 25,0
1,3 - 2,5
13 - 25,0
1,3 - 2,5
LPG
mbar
kPa
25 - 57,5
2,5 - 5,75
25 - 57,5
2,5 - 5,75
25 - 57,5
2,5 - 5,75
25 - 57,5
2,5 - 5,75
Sound power level
(to EN ISO 15036-1)
At partial load
dB(A)
31,9
31,9
31,9
31,9
At rated heating output (DHW
heating)
dB(A)
42,3
42,3
46,1
48,4
Power consumption
(in the delivered condition)
W
38
45
64
110
*4
Appliances for multiple connection of type B1HF-[kW]-M and B1KF-[kW]-M
*2
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor up-
stream of the system.
Specification
Specification
6167586
Service