62
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
Enabling instantaneous heating water heater for DHW heating
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for ventilation
Parameters
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Vitovent 300-F
"2"
Vitovent 200-C
Other enabling settings, if applicable:
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"1"
"Enable reheater bank hydraulic 7D02"
"1"
"Enable humidity sensor 7D05"
"1"
"Enable CO2 sensor 7D06"
"1"
If necessary, set values:
"Ventilation"
Ó
"Set extract air temperature 7D08"
(only in conjunction with
Vitovent 300-F)
"100"
to
"300"
(
≙
10 to 30 °C)
"Flow rate reduced ventilation 7D0A"
Subject to sizing
Ventilation unit service instruc-
tions
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5700 582 GB