Vienybė-PK1
Brick wall
Front shield
5
0
Rockwool
S 30...50
Metal sheet
3
0
0
150
300
Pic. 2.
3.1.
Fire safety requirements
-
A 400x850 mm metal sheet must be placed on the flammable floor in front of the mouth;
-
The heater must be connected to the chimney which
should meet construction
standards and rules
and thrust of which is at least 10 Pa.
-
For the connection of the heater to the chimney steel pipes must be used, thickness
of which must be at least 1.5 mm.
-
The chimney must meet construction standards and regulations.
-
The installed and connected heater must be approved by a fire safety specialist;
-
The heater must not be installed on the wooden floor; the floor must have at least
50 mm thick concrete cover with a metal sheet on top.
-
The heater must be placed only next to the brick wall of the sauna;
-
The minimum distance between the heater and walls/ceiling of the sauna is shown
in Pic. 2 and 3.
-
The heater must be installed in a way that it would be possible to replace it without
breaking down the walls of the sauna, i.e. the distance between the back of the heater and
the wall must be at least 300 mm., the duct of the mouth must pass through the opening in
the wall freely after the front panel of the door is removed;
-
The duct of the mouth of the heater must have at least 30 mm thick rock wool insulation;
-
Wooden ceiling must have at least 50 mm thick layer of rock wool insulation which
must be covered with a sheet of galvanized steel or aluminum (see Pic. 3).
20
Vienybė-PK1 (13.02) V2 LT, RU, EN