Product Instructions

Basic Digital Setpoint Control II

PI-PR-17023 05/08

3 of 5

Programming

Once the control is powered on 
press "MENU" button on the control 
keypad to adjust settings:

At any point during the 
programming you may press the 
"HOME" button to return back to the 
sensor viewing.

 1.  Press "MENU", then press the 

right arrow button when the    
"Program Screen" appears

 2.  When the "Relay Screen"            

appears, press right arrow to  
select Relay 1  

 3.  Scroll up or down to select     

"Setpoint 1" then press the right 
arrow button

 
 4.  Using the up and down 
 

arrows to adjust the 

 

Setpoint 1 desired setpoint 

 

-40 - 248 °F (this is the 

 

maximum slab temperature 

 

setting of the heating and or 

 cooling 

system)

 
 5.  Once the setpoint has been    

adjusted press the right arrow 
button  to accept and to display 
the "Relay 1" menu

 
 6.  Select "Diffrntl" by pressing the 

right arrow button

 
 7.  Using the up and down arrows, 

adjust the differential, the range 
is 1 - 150°F, once selected 
press the right arrow to accept 
and return to "Relay 1"  menu

 

 
8.  Select "Sensor A or 
 

Sensor B" for "Relay 1" 
using  the up and down 

 

arrows, then press right 
arrow button to accept

9.  Select "Heat / Cool" option 

for "Relay 1" then press 
right arrow button

10. Once you have completed 

all of the steps either press 
the "HOME" key or scroll 
down using the down arrow 
to "EXIT" and then press the 
right arrow button

11. Repeat all steps to 
 

confi gure "Relay 2"

 

Once all programming is 
complete the confi guration 
can  be  locked  to  prevent  any              
unauthorized changes. 

To Lock or Unlock the key-
pad simply press and hold the 
"MENU" and "HOME" 
buttons simultaneously for fi ve 
seconds.

Operation

Heating Mode

In heating mode once the slab 
temperature reaches the selected 
setpoint temperature the relay 
will be de-energized.  As the slab 
temperature decreases below the 
selected differential the relay will 
energize. 

Example: Slab setpoint is set to 
85 °F differential is set to 5, once 
the slab  temperature is below 
80 °F the relay will be energized.

Cooling Mode

In cooling mode, the differential 
is above the setpoint.  So as the 
temperature rises higher than the 
selected setpoint plus the 
differential the relay is energized.

Example: Slab temperature is 
set to  66 °F with a differential 
of 2. When the slab temperature 
reaches 68 °F the relay will be 
energized.

Содержание ProRadiant SYSTEMS Basic Digital Setpoint Control II

Страница 1: ... basic heating and or cooling system control for commercial and residential slab application Features Setpoint Control for Heating and Cooling Simple installation and programming Large digital LCD display Reliable economical Two relay outputs with individual Setpoint capability Watertight Sensor included Specifications Digital Setpoint Control II with watertight sensor 17029 Watertight Sensor 1703...

Страница 2: ... 120V 240V SUPPLY RELAY 1 RELAY 2 Wiring Digital Input LOAD 2 LOAD 1 Sensor A is triggering the two relays Relay 1 being boiler circulator pump and Relay 2 being system circulator pump In heating mode when the sensor detects temperature lower than the selected setpoint minus the selected differential both relays will be energized When the temperature reaches the setpoint the relays will de energiz...

Страница 3: ...the right arrow to accept and return to Relay 1 menu 8 Select Sensor A or Sensor B for Relay 1 using the up and down arrows then press right arrow button to accept 9 Select Heat Cool option for Relay 1 then press right arrow button 10 Once you have completed all of the steps either press the HOME key or scroll down using the down arrow to EXIT and then press the right arrow button 11 Repeat all st...

Страница 4: ...f the setpoint configuration is correct disconnect the sensor and check its resistance Replace the sensor if its resistance value does not match the temperature in the accompanying chart to the right Temp F Temp C Resistance Ohms 40 40 0 851 30 34 4 872 20 28 8 893 10 23 3 914 0 17 7 935 10 12 2 956 20 6 6 977 30 1 1 998 40 4 4 1019 50 10 0 1040 60 15 5 1061 70 21 1 1082 80 26 6 1103 90 32 2 1124 ...

Отзывы: