Installation Instructions
25 of 38
IM-PP 724607 1218 ProPress
Tube
Diameter
(inches)
Soldering
minimum
distance (inches)
Soldering
minimum
distance (mm)
Brazing minimum
distance (inches)
Brazing minimum
distance (mm)
½
1½
38
4½
114
¾
2¼
57
6¾
172
1
3
76
9
229
1¼
3¾
95
11¼
286
1½
4½
114
13½
343
2
6
153
18
457
2½
7½
191
22½
572
3
9
229
27
686
4
12
305
36
915
Table 18: Minimum distance between existing ProPress fitting and soldered or brazed fitting
The installer should take precautions to keep the Viega ProPress
connection cool:
■
Wrap the connection with a cold wet rag.
■
Protect the connection with a weld blanket.
■
Prefabricate solder connections/welded fittings prior to installing the
press fitting. (Ensure tube has cooled before installing the fitting).
■
Apply heat sink gel or spray or spot freezing
4.5 Welding
To prevent damage to the sealing element, maintain proper welding
distances from the fitting. If welding adjacent to the connection, weld a
minimum of four inches away.
Installers should follow the precautions listed above to keep the Viega
ProPress connection cool.
4.5.1 Welding Adjacent to a Fitting
To prevent damage to the sealing element, maintain proper welding
distances from the fitting. If welding in line with the connection, weld a
minimum of three feet away from the connection to protect the sealing
element.
Installers should follow the precautions listed above to keep the Viega
ProPress connection cool.
4.5.2 Welding In Line with a Fitting