When using cables under 8 m in length, only attach jumper to one
contact (see graphic, factory condition).
The control unit is provided with two potential-free outlets, through
which acoustic and optical alarm devices can be connected.
Both contacts function as N.O. The alarm contact (clamping strip con‐
nection 7/8) at
"
Rück
"
(Back) is closed in the event of backflow. The
fault indicating contacts (clamping strip connection 9/10) at
"
Stör
"
(Fault) closes when an operating fault is reported.
Observe the following when connecting on-site alarm devices:
n
When allocating the contacts, ensure that a maximum current of
500 mA / 24 V is not exceeded.
n
Allocation of the outlets must only take place using safety low
voltage and galvanic separation of the network.
n
Only connect purely ohmic loads.
n
The use of a safety transformer in accordance with VDE 0551 or
DIN EN 60742 is permitted.
3.3
Commissioning
3.3.1
Commissioning the control
As soon as the mains voltage is connected, the control begins the auto‐
mated commissioning process.
Display: [Commissioning]
There is a self-test of the rechargeable battery, mains connection and
motor control components. The motor-powered flap is opened and
closed once.
After a successful self-test, the control switches to normal operation -
the motor-powered flap is opened.
Display: [Normal operation / NRV opened]
Faults detected during the self-test are shown on the screen.
3.5 ‘Errors, faults and remedy’ on page 31
Date and time must be set after the initial commissioning,
as a prerequisite that the maintenance reminder, error log‐
ging and daily self-test can function.
‘Operating condition - normal operation’ on page 26
Alarm and fault indicating contacts (optional)
Handling
Grundfix Plus Control backflow trap type 3
22