background image

Viega... The global leader in plumbing and heating systems.

301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: [email protected] • www.viega.com

PI-PR-18050-0309 (Digital Thermostat)

Product Instructions

Digital Thermostat

4 of 4

Advanced Wiring of Digital Thermostats

NTC  A/B

C C R W

 24 VAC

TRANSFORMER

 120 VAC

INPUT

WHITE

BLACK

Optional

Floor sensor

Wiring Floor Sensor

The Digital Thermostat Floor Sensor is a 
two wire, water-sealed probe that can be used to 
accurately measure slab or floor temperatures. 
Floor Sensor should be placed in conduit for 
protection and repair. 1/2" PEX (capped or 
plugged) is commonly used as conduit for the slab 
sensor. Sensor should be 18" from line voltage 
(110V). If crossing line voltage wire cross at 90° 
angle. Line voltage interference can result in 
inaccurate readings of the sensor.

Connect one wire of the floor sensor to one 

1. 

"NTC" terminal of the Digital Thermostat.
Connect the other wire of the floor sensor 

2. 

to the other "NTC" terminal of the Digital 
Thermostat.

(See diagram to right)

Wiring External Clock

The Digital Thermostat is compatible with an 

external clock for timed set-back. Press the "OK" 

button to select the     External Clock Mode. 

The thermostat display indicates weather it's in 

Comfort Mode or Reduced Temperature Mode by 

blinking the     or      symbols.

Powerhead(s) and Transformer

Connect "R" terminal of the thermostat to the 

1. 

transformer.
Splice into the "R" terminal wire and connect 

2. 

that to inlet side of an external clock. 
Connect the outlet side of the external clock 

3. 

to A/B terminal on right side of thermostat.
Connect the "W" terminal of the thermostat to 

4. 

powerhead(s). 
Connect a "C" terminal of the thermostat to 

5. 

the  powerhead(s). 
Connect a "C" terminal of the thermostat to 

6. 

the transformer.

(See diagram top right)

Zone Control

Connect "R" terminal of the thermostat to the 

1. 

"R" of Zone Control.
Splice into the "R" terminal wire and connect 

2. 

that to inlet side of an external clock. 
Connect the outlet side of the external clock to 

3. 

A/B terminal on right side of thermostat.
Connect the "W" terminal of the thermostat to 

4. 

"W" of the Zone Control.
Connect a "C" terminal of the thermostat to the  

5. 

"C" of the Zone Control.

(Not shown)

Temperature

Resistance (k

)

50°F

~ 19.5k

59°F

~ 15.5k

68°F

~ 12.5k

77°F

~ 10k

86°F

~ 8k

 Resistance Chart

Содержание Digital Thermostat

Страница 1: ...for energy savings Thermostat can control up to four Powerheads directly or can be connected to a zone circulator control box With optional floor sensor thermostat provides floor high or low limit function for floor protection or floor warming Features Compact design Digital LCD display Regulates floor or room temperature or both Optional Floor Sensor Setback function Specifications Control Accura...

Страница 2: ...tted mounting holes simplifying leveling of the thermostat Thermostats should be installed with sleeves and anchors when mounting into drywall Connect the R terminal of the thermostat 1 to the R terminal of the Zone Control R supplies power to the thermostat Connect the W terminal of the thermostat to 2 the W terminal of the Zone Control W is the switching signal Connect the C terminal of the ther...

Страница 3: ...on default 41 F effective only if floor sensor is connected FH Floor temperature HIGH limitation default 82 F effective only if floor sensor is connected CLr Press OK button for 5 continuous seconds to restore default settings End Press OK button to exit the programming mode and return to user display Programming To program the Viega Digital Thermostat press the OK button for 5 continuous seconds ...

Страница 4: ...Wiring External Clock The Digital Thermostat is compatible with an external clock for timed set back Press the OK button to select the External Clock Mode The thermostat display indicates weather it s in Comfort Mode or Reduced Temperature Mode by blinking the or symbols Powerhead s and Transformer Connect R terminal of the thermostat to the 1 transformer Splice into the R terminal wire and connec...

Отзывы: